Top Vent - Horizontal Termination - (continued)
Two Elbows
Note: Use SLP Series
components only.
Note: There MUST be a 25%
reduction in total H when using
fl ex vent except when using the
simple up and out installation
(see Figure 5.3).
WARNING *
Fire Risk.
• When using SLP-HRC-SS and SLP-HRC-ZC-
SS termination caps on top vented fi replaces,
a one foot minimum vertical vent section is
required before installing fi rst elbow.
• When using DVP-TB1 termination cap on top vented
fi replaces, a three foot minimum vertical vent section is
required before installing fi rst elbow.
Figure 7.5
Heat & Glo • SL-750TRS-IPI-E, SL-550TRS-IPI-E, SL-350TRS-IPI • 2120-901 Rev. G • 11/08
28
1/2 ft.*
1-1/2 ft.*
2-1/2 ft.*
3-1/2 ft.
4-1/2 ft.
H
2
INSTALLED
HORIZONTALLY
V Minimum
90º Elbow
152 mm
457 mm
762 mm
1.1 m
1.4 m
H
+ H
Maximum= 14 ft. (4.3 m)
1
2
V
+ H
+ H
Maximum= 40 ft. (12.2 m)
1
1
2
* See warning below
H
1
H Maximum
SL-350TRS-IPI, SL-550TRS-E, SL-750TRS-E
NOT ALLOWED
1 ft.
2 ft.
4 ft.
6 ft
14 ft.
V
1
305 mm
610 mm
1.2 m
1.8 m
4.3 m