7100FP EPA Woodburning Fireplace
6
Complete the Enclosure
A. Chimney Termination (2-10-03 Rule)
Chimney Termination Requirements
Must have a cap approved and listed for this fireplace system
Must not be located where it will become plugged by snow or other material
Must terminate at least 3 ft (914 mm) above the roof and at least 2 ft (610 mm) above any portion of the roof within 10 ft
(3.05 m)
Must be located away from trees or other structures
Pitched Roof
3 ft. (91cm)
Minimum
Flat Roof
Figure 26.1 Termination Requirements
Page 26
(See Figures 26.1 and 26.2)
2 ft. (61cm)
10 ft. (305cm) To Nearest Roofline
10 ft. (305cm) or more
Wall or Parapet
3 ft. (91cm) Minimum
Gas, Wood or Fuel
Oil Termination
18 in.
(457 mm)
Gas
Termination
Termination Caps Staggered Height
A Gas Termination Wood or Fuel Oil Termination
B
6 in.
(152 mm) min.
Figure 26.2 Multiple Chimneys
433-1390G
Less than 10 ft. (305cm)
2 ft. (61cm)
2 ft. (61cm)Minimum
3 ft. (91cm) Minimum
8 ft
(2.44 m)
A
(min. for B-Vent)
20 in.
(508 mm)
(min. for direct vent)
B
to
Perpendicular
Wall
20 in.
(508 mm) min.
3 ft. (91cm)
Minimum
Less than 10 ft. (305cm)
September 1, 2008