Table B-2: NetAXS-123 SW2 DIP Switch Settings

a
S1
OFF
ON
a. Both DIP Switch 1 and DIP Switch 2 need to be either ON or OFF to be properly
configured.
: When you use the DIP switches to reset a panel to the original factory default
Note
values, the Event History is lost and any customized databases are removed, so the
panel is reset with the original factory default database. This does not affect the
Ethernet IP address.
You can also use the ASCII command _I=pn_R to reset a panel to the original
factory default values, but this command only removes the customized databases
and restores the original factory default database. The Event History is retained.
To reset the panel to the factory default values:
1. Make a note of the existing settings on SW1 DIP switches.
2. While the panel is powered up, turn all of the DIP switches to the OFF
3. Power down, then power the panel back up.
4. Wait for the panel to come up. The RUN LED should flicker fast.
5. Set the DIP switches back to their original positions.
6. Power down, then power the panel back up.
7. The RUN LED should flash normal.
The panel is now reset to the original factory default values.
NetAXS-123 Access Control Unit User's Guide, Document 800-05168, Revision B
a
Selection
S2
OFF
RS-485_2 termination (EOL) DISABLED (Default)
ON
RS-485_2 termination (EOL) ENABLED (FUTURE)
position.