Powering Up the System for the First Time

After the system is configured, the system may be powered up. If the system uses multiple Transponders it is
easier and more effective to power up the Transponders one at a time. By doing this troubleshooting time can be
significantly reduced, especially if there is a wiring problem in the SE485 bus between Transponders.
NOTE: It is very important that twisted pair wiring is used for the SE485 bus. The Tx+ and Tx- wires must be
twisted together and the Rx+ and Rx- wires must be twisted together.
1.
Turn on the power switch on the first Transponder. In the Security Escort Central Console software go to the
Setup menu and select Transponder Current Status. The following window will appear:
2.
Select the desired Transponder. Click the Reset Transponder Troubles button. If the selected
Transponder is communicating with the Central Console, the number 1 will appear in the Total Outgoing
Messages field and in the Successful Incoming Messages field. The Transponder is now communicating
with the Central Console software. If the number 1 only appeared in the Total Outgoing Messages field
there is a wiring problem between the Central Console and the Transponder (refer to Section 0,
Troubleshooting Reference, of this manual and locate the problem).
3.
Check the Stress Test box. This tests the communications reliability by causing the Central Console
software to send a continuous stream of messages to the selected Transponder. The values in the
Successful Incoming Messages and Total Outgoing Messages fields should start counting up rapidly,
with few if any errors. It is normal to have slightly fewer Total Outgoing Messages than Successful
Clicking this button will copy the displayed point or area data to a "clipboard" and clear all
values to default.
Clicking this button will copy the displayed point or area data to a "clipboard". Displayed
values will not be changed.
Clicking this button will copy the "clipboard" values to the displayed point or area data. The
values on the "clipboard" will not be changed and may be copied to more points or areas.
Clicking this button will save all changes to the database.
Figure 22: Current Transponder Status Window
Security Escort Training
Page 63 of 142