Honeywell C6097A Instruction Sheet page 4

Gas pressure switches universal gas valves

Advertisement

Accurate pressure set point adjustment
(stand alone only)
(tolerance
<
3%
over total scale)
1. Remove the screw from the test nipple inlet.
2. Connect the tube of the pressure measurement device
to the nipple (Fig. 1. F).
3. Remove the cover of the pressure switch.
4. Slowly release pressure of the main gas supply line until
the desired value is reached.
5. Turn dial slowly until contact 1-3 opens and contact
2-3 closes.
6. Replace the cover.
7. Disconnect the pressure measurement device and
replace the screw.
Checkout
Checking cut-off pressure
After the installation is completed, continue with the following
procedures:
1. Slowly close manual main valve with the burner in
operation. Shut down should occur when the pressure
drops below the set point and the alarm (if connected)
should be energized.
2. Re open the manual main valve. The pressure should
rise and exceed the set point value, the burner should
start up and the alarm turn off after the reset button is
depressed.