Section [900] Special Installer Instructions
Section [900]: Display Panel Version
Only available with LCD5500 or PK5500 keypads. The system will display the version of the control panel (for example, [0410] indicates
panel version 4.10).
Section [901]: Installer Walk Test
The system will turn Installer Walk Test ON. The Ready, Armed and Trouble LED's will flash rapidly while the test is active. Every time a
zone is violated the system will activate the bell output for two seconds and log the event to the event buffer. To turn Installer Walk TestOFF
enter Section [901] again. The system automatically terminates the test of there is no zone activity for 15 minutes.
Section [902]: Module Supervision Reset
All modules are automatically detected within one minute after being connected to the Keybus. Enter Section [902] to clear detected mod-
ules if a module is removed, if PC5108 jumpers are changed, or if a keypads slot assignments are programmed. The system will rescan the
Keybus to determine which modules are connected.
Section [903]: View Module Supervision
The keypad will display the modules detected by the system by turning on the associated zone light (LED keypads), flashing the numbers
(fixed-message LCD keypads) or displaying the modules detected in plain language (programmable LCD keypads). Refer to the chart
below:
Indicator Light
(Zone)
[01] to [08]
[09] to [14]
[15]
[16]
[17]
[18]
[19]
[20]
[21]
[22]
[24]
[26] to [29]
Section [904]: Wireless Placement Test
Enter Section [904] followed by the 2-digit number of the wireless zone to test. When a wireless signal is received from the selected trans-
mitter, the system will indicate the location as Good or Bad as follows:
Good:
One bell squawk, 1 keypad beep, keypad zone light [1] ON
Bad:
Three bell squawks, 3 keypad beeps, keypad zone light [3] ON
Press [#] to exit when testing is complete. Enter the 2-digit zone number for the next wireless device to test or press [#] to return to standard
programming.
Section [990]: Installer Lockout Enable
Enter Section [990][Installer Code][990] to enable the Installer Lockout feature. A hardware default cannot be performed when the
Installer Lockout feature is ON. In addition, the system will chatter the line seizure relay 10 times if the panel is powered up to indicate the
feature is ON.
Section [991]: Installer Lockout Disable
Enter Section [991][Installer Code][991] to turn the Installer Lockout feature OFF.
Module
Keypad in Slot #1 to #8
PC5108 Zone Expander #1 to #6
PC5100 Module
PC5108 Zone Expander #7
PC5132 Module or RFK keypad with integrated wireless receiver
PC5208
PC5204 Module
PC5400 Module
PC59xx Module
Alternate Communicator
Escort5580 or Escort5580TC
PC5200 #1 to #4
Section 4 – Programming Descriptions
23