Chimney Termination Requirements; Outside Air Requirements - Lopi Answer Owner's Manual

Wood stove / inbuilt
Hide thumbs Also See for Answer:
Table of Contents

Advertisement

Stove Installation

Chimney Termination Requirements

Must have an approved cap (to prevent water from entering).
Must not be located where it will become plugged by snow or other material.
Must terminate at least 3' (914mm) above the roof and at least 2' (610mm) above any portion of the
roof within 10' (3.04M) - see Figure 5.
Min. 3' (914mm)
Min. 3' (914mm)

Outside Air Requirements

Required for mobile homes & in certain localities (check with building officials).
Must not be drawn from an enclosed space (garage, unventilated crawl space).
Requires the optional outside air connector or pedestal.
Air duct maximum length is 15' (4.57M) with a minimum cross-section of 16 square inches
(10404mm) or 6' (1.82M) with a minimum cross section of 7 square inches (4489mm).
Pedestal or outside air boot may
be used to direct air from below
the stove. See the pedestal
instructions for complete details.
Air may be drawn from a ventilated
crawl space or use an air duct.
© Travis Industries
(for qualified installers only)
Min. 2' (610mm)
10' (3.04M)
Min. 2' (610mm)
The pedestal has an air
opening for use with the
outside air connections.
This allows air to be
drawn from behind the
pedestal.
Outside air entrance must be placed so
it does not become blocked by snow.
100-01278
10' (3.04M)
Outside Air
Connector
11
Figure 5
Figure 6
4111128