Refrigeration System - Payne PA13NR018 Installation Instructions Manual

Pa13nr split-system air conditioner for use with r-22 refrigerant
Table of Contents

Advertisement

REFRIGERATION
SYSTEM
A. COMPONENT
MATCHES
Check
to see that
the proper
system
components
are in place,
especially
the indoor
coil.
R-22
outdoor
units
can only
be used with R-22
specific
indoor
coils. If there
is a refrigerant
mis-match,
consult
the indoor
coil
manufacturer
to
determine
if
a refrigerant
conversion
kit
is
available
for the indoor
coil.
This outdoor
unit is designed
for use only with indoor
coils that
utilize
a TXV
refrigerant
metering
device.
If any other
type
of
metering
device
is installed
on the indoor
coil, consult
the indoor
coil manufacturer
to determine
if a TXV conversion
kit is available
UNIT
OPERATION
HAZARD
Failure
to follow
this caution
may result
in improper
unit
operation.
This
unit
utilizes
R-22
refrigerant.
Use
only
R-22
refrigerant
when servicing
this unit.
DO NOT
under
any circumstances
use R-410A
refrigerant
in this system.
When installing
a TXV
on an indoor
coil, follow
the instructions
provided
with the new TXV.
A typical TXV installation
is shown
in Fig. 3.
B. REFRIGERANT
LINE
SETS
The refrigerant
line set must be properly
sized to assure maximum
efficiency
and proper
oil circulation.
Refer
to Long Line Guideline
for line set sizing.
NOTE:
Total line set length
must not exceed
200 feet (61 m).
A crankcase
heater
must be used when
the refrigerant
line length
exceeds
80 feet (24.4 m).
If vertical
separation
between
indoor
and outdoor
units
is greater
than 30 ft (9.14
m), refer to the Long Line Guideline.
If it is necessary
to add refrigerant
line in the field, use dehydrated
or dry, sealed,
deoxidized,
copper
refrigeration
tubing.
Do not use
copper
water pipe.
Do
not remove
rubber
plugs
or caps
from
copper
tubing
until
connections
are ready to be made.
Be extra
careful
when
bending
refrigeration
tubing.
Tubing
can
"kink"
easily, and if this occurs,
the entire length
of tubing must be
replaced.
PERSONAL
INJURY HAZARD
Failure to follow this warning could result in personal injury
and/or death,
Relieve pressure and recover all refrigerant before servicing
existing equipment, and before final unit disposal, Use all
service ports and open all flow-control
devices, including
solenoid valves,
EQUALIZER
TUBE
SENSING
SUCTION
BULB
TUBE
TXV
SENSING BULB
(EITHER SIDE)
N
8 O'CLOCK
4
Fig. 3 - Typical TXV Installation
LIQUID
TUBE
STRAP
O'CLOCK
UNIT
OPERATION
HAZARD
Failure
to follow
this caution
may result
in improper
unit
operation.
Do not leave system
open to atmosphere
any longer
than
absolutely
required
for
installation.
Internal
system
components
- especially
refrigerant
oils - are extremely
susceptible
to moisture
contamination.
Keep ends of tubing
sealed during
installation
until the last possible
moment.
C. ROUTING
AND SUSPENDING
REFRIGERANT
LINES
Run refrigerant
lines
as straight
and direct
as possible,
avoiding
unnecessary
bends
and turns. Always
insulate
the entire suction
line. Both lines should
be insulated
when routed through
an attic or
when routed
through
an underground
raceway.
When routing
refrigerant
lines through
a foundation
or wall, do not
allow refrigerant
lines to come in direct contact
with the building
structure.
Make
openings
large enough
so that lines
can be wrapped
with
extra
insulation.
Fill all gaps with
RTV caulk.
This
will prevent
noise transmission
between
the tubing and the foundation
or wall.
Along
floor or ceiling
joists,
suspend
refrigerant
lines so that they
do not contact
the building
structure,
water pipes, or ductwork.
Use
insulated
or suspension
type hangers.
Metal straps must be at least
1" (25 mm) wide to avoid cutting
into the tube insulation.
Keep the
liquid
and suction
lines separate.
Refer to Fig. 4.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pa13nr024Pa13nr036Pa13nr030Pa13nr042Pa13nr048Pa13nr060

Table of Contents