Download Print this page

Payne PYIP180040 Installation, Start-Up And Service Instructions Manual page 4

Py1p single packaged gas heating/ electrical cooling units

Advertisement

(19,0)
(55,B)
DRAIN OUTLET
FRONT VIEW
RETURN
AIR OPENING
14 71IS"
(365.91
l
_'2 1/lS"
(52,6)
10 9/16 °
(268,9)
FLUE
HOOD
18 1/16
(458,8)
(E8,0)
t
3116 _
129.GI
0 7/8"
(22.23)
1 1/4" (31.?51
ALTERNATE L V ENTRY ALTERNATE P OWER E NTRY
EVAPCOIL ACCESg
(292.
I )
1325.4)
(36,
3)
(253,81
LEFTSIDE VIEW
REQ'D CLEARANCES
FOR SERVICING.
in (ram)
Duct panel .............................
0
Unit top ...........................
36 (914)
Side opposite
ducts
.....................
36 (914)
Compressor
access
.....................
36 (914)
(Except for NEC requirements)
REQ'D CLEARANCES
TO COMBUSTIBLE
MAT'L. in (ram)
Maximum
extension
of overhangs
...............
48 (1219)
Unit top ...........................
14 (356)
Duct side of unit
........................
2 (51)
Side opposite
ducts
.....................
14 (356)
Bottom of unit
...........................
0
Flue panel
.........................
36 (914)
NEC REQ'D CLEARANCES.
in (ram)
Between
units, control box side ................
42 (1067)
Unit and ungrounded
surfaces,
control box side
.........
36 (914)
Unit and block or concrete walls and other grounded
surfaces,
control box side
..................
42 (1867)
718" (22.2)DIA,
I I18" (28.6) OIA.
CONTROL ENTRY
POWER ENTRY
28
15/16
1734
'
I
I
1 5/9"
(41.9)
OIA, _-_
GAS
ENTRY
I/2"- 14 NPT
GASOONNECT!0N
i
FLUE
PANEL
UNIT
ELECTRICAL
CHARACTERISTICS
PY1PO48080
208/230-1-60,
208/230-3-60,460-3-60
PY1P048100/120/140
208/230-1-60,
208/230-3-60,460-3-80
PY1P060080
208/230-1-60,
208/230-3-60,460-3-80
PYIP060100/120/140
208/230-1-60,
208/230-3-60,460-3-80
UNIT
PYIP048080
PYIP048100/120/140
PYIP060O80
PYIP060100/120/140
CENTER
OF GRAVITY
(in./mm)
UNIT WEIGHT
Ib
kg
414
188
426
193
453
206
465
211
A
107/49
110/50
117/53
120/55
CORNER
WEIGHT
(Ib/kg)
B
C
83/38
158/72
86/39
159/72
93/42
167/76
96/44
167/76
LEGEND
CG
--
Center of Gravity
MAT'L
--
MateriaI
X
Y
28.76/731
2346/596
28.42/722
2342/595
28.36/720
2327/591
27.95/710
2323/590
D
66/30
71/32
76/35
82/37
Z
1535/390
1535/390
1535/390
1535/390
COND
--
Condenser
NEC
-- National Electrical
Code
LV
--
Low Voltage
REQ'D
-- Required
NOTES:
1. Clearances must be maintained to prevent recircutation of air from outdoor-
fan discharge.
2 Adequate clearance around air openings into combustion
chamber must
be provided.
Fig. 4 --
PYIP048,060
Without
Base
Rail, Unit
Dimensions
--4--

Advertisement

loading