Payne PYIP180040 Installation, Start-Up And Service Instructions Manual page 29

Py1p single packaged gas heating/ electrical cooling units

Advertisement

Table 10 -- Dry-Coil Air Delivery* -- Downflow Discharge at 230 and 460 V -- Unit PYIP
(Deduct 10% from Cfm and Watts for 208 V Operation)
UNIT
MOTOR
AIR
EXTERNAL
STATIC PRESSURE
(in. wg)
PYIP
SPEED
DELIVERY
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0,7
0.8
0.9
1.0
Watts
t
295
251
223
201
176
149
!24
t
t
Low
Cfm
t
821
817
753
665
536
343
164
t
t
018
Watts
401
376
346
322
294
272
250
229
219
t
High
Cfm
!334
1253
1128
996
816
658
461
246
167
t
Watts
t
285
284
282
278
274
270
261
251
244
230
Low
Cfm
t
798
76!
727
682
634
581
525
450
37!
304
024,
Med
Watts
t
378
371
368
362
357
343
332
315
301
283
030
Cfm
t
!01!
982
948
906
858
771
703
597
492
387
Wafts
t
520
51!
487
472
451
431
411
385
362
341
High
Cfm
t
1342
!309
1237
1181
1106
1007
892
745
610
471
Wafts
t
460
439
423
398
379
349
322
297
270
246
Low
Cfm
t
!19!
1136
1081
!005
907
795
687
579
47!
349
Watt
t
511
492
470
450
420
392
364
332
308
275
036
Med
Cfm
t
1316
1244
!178
1104
1005
891
784
657
535
389
Watts
_
655
631
603
584
552
522
492
459
433
398
High
Cfm
?
!54!
1458
!367
1292
1178
1053
920
806
662
509
Wafts
_
637
612
587
560
526
493
455
t
t
t
Low
Cfm
_
!500
1450
1405
1350
1290
1200
1105
t
t
t
042
Wafts
_
790
750
700
679
639
608
574
547
t
t
High
Cfm
_
1750
1675
!604
1509
1421
1323
1221
1094
t
t
Watts
_
847
784
746
708
646
609
563
516
t
t
Low
Cfm
_
1995
1901
!822
1730
1580
1477
1319
1!78
t
t
048
Watts
_
t
909
852
820
801
751
687
639
t
t
High
Cfm
_
t
2018
!896
18!4
1729
1582
1380
1270
t
t
Wafts
_
983
950
923
885
845
804
751
697
665
633
Low
Cfm
_
1838
1808
1755
1702
!628
1553
1446
1339
1257
1175
Wafts
?
1115
1083
!045
1006
964
921
872
823
783
742
060
Med
Cfm
?
2067
2023
!957
1891
!807
1723
1612
150!
1392
!282
Watts
?
1284
1201
1166
!131
!092
1053
1001
950
907
864
High
Cfm
?
2167
2108
2038
1968
1882
1796
1676
1555
1437
!318
*Air delivery values are without air filter and are for dry coil. See
Table 11 for wet coil pressure drop. Deduct field-supplied
air filter
pressure drop and wet coiI pressure drop to obtain external static
pressure available for ducting.
1-Unit air delivery is outside of operating range.
NOTE:
Do not operate the unit at a cooling airflow that is less than
350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator-
coil icing may occur at airflows below this point. Water blow-off may
occur at airflows above 450 cfm per 12,000 Btuh of rated cooling
capacity.
Table 11 -- Wet Coil Pressure Drop
UNIT SIZE PYIP
018
024
030
036
042
O48
060
AIRFLOW(cfm)
600
700
8OO
900
600
700
8OO
900
900
1000
1200
1000
1200
1400
1600
1000
1200
1400
1600
1400
1600
1800
1700
1900
2100
2300
PRESSURE
DROP (in. wg)
0.069
0.082
0.102
0.116
0.039
0.058
0.075
0.088
0.088
0.095
0.123
0.068
0.088
0.108
0.123
0.048
0.069
0.088
0.102
0.068
0.075
0.088
0.082
0.095
0.108
0.123
--29--