Payne PYIP180040 Installation, Start-Up And Service Instructions Manual page 28

Py1p single packaged gas heating/ electrical cooling units

Advertisement

Table 8 -- Required Suction-Tube
Temperature
(F)*
SUPERHEAT
SUCTION
PRESSURE
AT SERVICE PORT (psig)
TEMP (F)
61.6
64.2
67.1
70,0
73.0
76.0
79,2
82.4
86.7
0
35
37
39
4!
43
45
47
49
51
2
37
39
41
43
45
47
49
51
53
4
39
41
43
45
47
49
5!
53
55
6
41
43
45
47
49
51
53
55
57
8
43
45
47
49
51
53
55
57
59
10
45
47
49
51
53
55
57
59
61
12
47
49
51
53
55
57
59
6!
63
14
49
51
53
55
57
59
61
63
65
16
5!
53
55
57
59
61
63
65
67
18
53
55
57
59
61
63
65
67
69
20
55
57
59
8!
83
65
67
89
71
22
57
59
61
83
85
67
69
71
73
24
59
61
63
85
87
69
7!
73
75
26
81
63
65
87
89
71
73
75
77
28
83
65
67
89
71
73
75
77
79
30
85
67
69
71
73
75
77
79
81
32
87
69
71
73
75
77
79
81
83
34
89
71
73
75
77
79
8!
83
85
36
7!
73
75
77
79
81
83
85
87
38
73
75
77
79
81
83
85
87
89
40
75
77
79
8!
83
85
87
89
91
*Temperature at su_ion
service valve.
Table
9 -- Dry-Coil
Air Delivery*
--
Horizontal
Discharge
at 230 and 460 V --
Unit PYIP
(Deduct
10% from
Cfm and Watts
for 208 V Operation)
UNIT
MOTOR
AIR
EXTERNAL STATIC PRESSURE
(in. wg)
PY1 P
SPEED
DELIVERY
0,0
0.1
0.2
0.3
0.4
0.6
0.6
0,7
0.8
0.9
1.0
Watts
230
225
220
210
195
170
t
_
_
_
t
Low
Cfm
760
745
725
695
640
540
t
t
t
t
t
018
Watts
t
t
t
t
270
235
200
t
t
t
t
High
Cfm
t
?
t
?
850
700
450
t
?
t
?
Watts
275
275
273
269
260
257
249
?
?
?
?
Low
Cfm
857
835
802
782
745
717
663
t
?
_
?
024,
Med
Watts
371
368
360
349
345
326
319
304
293
?
030
Cfm
1079
1063
1027
996
978
919
865
783
726
_
Watts
5!4
493
476
460
443
425
40!
378
344
_
High
Cfm
!409
1383
1324
1282
1223
1!56
1068
984
857
_
Watts
473
447
427
418
395
367
346
337
323
_
Low
Cfm
!253
1253
1172
1130
1047
946
865
829
768
_
Watts
5!9
500
478
459
439
410
377
357
340
_
036
Med
Cfm
!414
1366
1287
1234
1162
!074
920
829
743
_
Watts
667
634
609
593
564
541
506
469
436
422
High
Cfm
1734
1639
1563
1461
1370
!292
1157
960
829
743
Watts
678
635
604
580
550
520
493
455
430
_
Low
Cfm
!540
15!5
1475
1430
1375
!280
1225
1128
1020
_
042
Watts
t
820
785
750
700
680
649
612
570
_
High
Cfm
t
1825
1750
1685
1610
1525
1485
!355
12!5
_
Watts
t
t
854
786
744
706
64!
606
557
511
Low
Cfm
t
t
2026
1905
1830
1752
1603
!513
1367
1228
048
Watts
t
t
_
905
846
824
804
748
683
637
High
Cfm
t
t
_
2025
1905
1830
1752
1603
1398
1228
Watts
!104
!093
1072
1029
986
938
89!
830
769
733
697
Low
Cfm
!876
1865
!840
1803
1765
1710
1641
!533
1425
!345
1264
Watts
1351
!295
1245
1197
1148
1096
1053
994
936
871
812
060
Med
Cfm
2249
2209
2157
2097
2036
1959
1882
!781
1679
1542
1405
Watts
t
t
1391
1343
1296
1247
1!91
!129
!067
1002
936
High
Cfm
t
t
2299
2231
2152
2060
!975
1859
!746
1591
1441
*Air delivery
values are without
air filter and are for dry coil. See
Table 1! for wet coil pressure drop. Deduct field-supplied
air filter pres-
sure drop and wet coil pressure drop to obtain external static pressure
available for ducting.
tUnit air delivery is outside of operating range.
NOTE:
Do not operate the unit at a cooling airflow that is less than
350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator-coil
icing may occur at airflows below this point. Water blow-off may occur at
airflows above 450 cfm per 12,000 Btuh of rated cooling capacity.
--28--