Download Print this page
Payne PYIP180040 Installation, Start-Up And Service Instructions Manual
Payne PYIP180040 Installation, Start-Up And Service Instructions Manual

Payne PYIP180040 Installation, Start-Up And Service Instructions Manual

Py1p single packaged gas heating/ electrical cooling units

Advertisement

Quick Links

CONTENTS
Page
SAFETY
CONSIDERATIONS
......................
1-5
I. General
...................................
1
RECEIVING
AND
INSTALLATION
.................
6 15
I. Step
1 -- Check
Equipment
..................
(3
II.
Step
2 -- Provide
Unit
Support
...............
(3
III.
Step
3 -- Field
Fabricate
Ductwork
............
(3
IV.
Step
4 -- Provide
Clearances
.................
6
V.
Step
5 -- Rig
and Place
Unit
.................
6
VI.
Step
6 -- Connect
Condensate
Drain
..........
9
VII.
Step
7 -- Install
Flue
Hood
...................
9
VIII.
Step
8 -- Install
Gas Piping
..................
9
IX.
Step
9 -- Install
Duct
Connections
...........
11
X.
Step
10 -- Install
Electrical
Connections
......
13
PRE-START-UP
.................................
1(3
START-UP
....................................
16 29
I. Check
for
Refrigerant
Leaks
.................
1(3
II.
Start-Up
Heating
Section
and
Make Adjustments
.........................
17
III.
Start-Up
Cooling
Section
and
Make Adjustments
.........................
20
MAINTENANCE
................................
3043
I. Air Filter
..................................
30
II.
Unit
Top Removal
..........................
30
III.
Evaporator
Blower
and Motor
................
30
IV.
Flue
Gas Passageways
.....................
31
V.
Combustion-Air
Blower
.....................
31
VI.
Limit
Switch
..............................
31
VII.
Burner
Ignition
............................
31
VIII.
Main
Burners
.............................
32
IX.
Condenser
Coil,
Evaporator
Coil,
and
Condensate
Drain
Pan
.....................
32
X.
Condenser
Fan
............................
33
XI.
Electrical
Controls
and Wiring
...............
33
Xll.
Refrigerant
Circuit
.........................
33
Xlll.
Gas Input
.................................
33
XlV.
Evaporator
Airflow
.........................
33
XV.
Metering
Device
-- Acutrol
TM
Device
..........
33
XVI.
Liquid
Line
Strainer
........................
33
TROUBLESHOOTING
...........................
34-3(;
START-UP
CHECKLIST
..........................
CL 1
NOTE
TO
INSTALLER
--
Before
the
installation,
READ
THESE INSTRUCTIONS CAREFULLY AND COMPLETELY.
Also,
make
sure
the
User's
Manual
and
Replacement
Guide
are
left
with
tile unit
after
installation.
The
furnace
is NOT
to be used
for temporary
heating
of buildings
or structures
under
constrttction.
SAFETY CONSIDERATIONS
Installation
and servicing
of air-conditioning
equipment
can
be hazardous
due to system
pressure
and
electrical
compo
nents.
Only trained
and qualified
personnel
should
install,
repair,
or service air conditioning
equipment.
Cancels: II PY1P 18 1
II PY1P
18 2
9/1/98
Fig. 1 -- Unit PY1P
Untrained
personnel
can perform
basic
maintenance
flmc-
tions of cleaning
coils and filters. All other
operations
should
be performed
by trained
service personnel.
When working
on
air conditioning
equipment,
observe
precautions
in the lit
erature,
tags and labels attached
to the unit, and other safety
precautions
that may apply.
Follow all safety
codes. Wear safety glasses
and work gloves.
Use quenching
cloth for unbrazing
operations.
Have fire ex-
tinguisher
available
for all brazing
operations.
I. GENERAL
The PY1P units
(see Fig. 1) are fidly self-contained,
combi-
nation
Category
I gas heating/electric
cooling units
designed
for outdoor
installation.
See Fig. 2 5 (pages 2 5) for unit
di-
mensions.
All unit sizes have discharge
openings
for both hori
zontal
and downflow
configurations,
and are factory shipped
with all 4 duct openings
covered.
Units
may be installed
ei-
ther on a rooftop or a groundqevel
cement
slab. See Fig. 6 for
roof curb dimensions.

Advertisement

loading

Summary of Contents for Payne PYIP180040

  • Page 1 Cancels: II PY1P 18 1 II PY1P 18 2 9/1/98 CONTENTS Page SAFETY CONSIDERATIONS ...... I. General ........RECEIVING INSTALLATION ....6 15 I. Step 1 -- Check Equipment ....Step 2 -- Provide Unit Support ....III. Step 3 -- Field Fabricate Ductwork ....
  • Page 2 REAR VIEW LEFT SIDE VIEW CORNER WEIGHT UNIT HEIGHT UNIT WEIGHT ELECTRICAL UNIT (Ib/kg) (in./mm) CHARACTERISTICS 81/37 82/28 78/35 53/24 24 1/813 PYIP180040 208/230-1-60 97/44 43/20 123/56 40/18 241/813 PY1P024040 208/230-1-60 100/45 46/21 128/57 43/20 241/813 PYIP024060 208/230-1-60 100/45 47/21...
  • Page 3 -45 I/2" COND COIL (115E,7) 43 11/16 ° 1 9/16" (II08.B) OPTIONAL RETURN AIROPENING 7" SLOWER ACCESS PANEL BURNER CONTROL RIGHT _IDE VIEW ACCESS PANEL 52" (1320_8) REQ'D CLEARANCES FOR SERVICING. in. (mm) (368.9) Duct panel ......Unit top ......36 (914) Side opposite ducts...
  • Page 4 0 7/8" (22.23) 1 1/4" (31.?51 ALTERNATE L V ENTRY ALTERNATE P OWER E NTRY FLUE HOOD EVAPCOIL ACCESg RETURN AIR OPENING 18 1/16 (458,8) 14 71IS" (365.91 (E8,0) _'2 1/lS" (52,6) 3116 _ 10 9/16 ° 129.GI (292. 1325.4) (36, (268,9) (253,81...
  • Page 5 114" 1/2" (31,7G3 CON0 C0IL (115B,71 ALTERNATE POWER ENTRY 11/16" (23, B) 1110B.8) EVAP COIL ACCEBB FLUE HO00 OPENING /16" 1B 1/15 14 ?/16" (458.8) (355.9) B 518" (142.9) 1116" (52,6) BilE" (268.91 1B/16: "_ (29.5) (253.5) REQ'D CLEARANCES FOR SERVICING. in.
  • Page 6 RECEIVING AND INSTALLATION Insulate attd weatherproof all external ductwork, joints, attd roof openings with counter flashing and inastic in accordance I. STEP 1 -- CHECK EQUIPMENT with applicable codes. A. Identify Unit The unit model nmnber and serial number are stamped unit identification plate.
  • Page 7 PART NUMBER CPRFCURB001A01 8" [203] FLAT CPRFCURB002A01 11" [279] CURB CPRFCURB003A01 14" [356] POWER AND GAS ENTRY SUPPLY OPENING "0 [44E] RETURN OPENING [SEE DETAIL "A "j [279 (406] 5UPPLY [13] 3G 3/4". SCREW DLEARANOE [1010] THIS BRACKET MUST BE REMOVED MUST BE REMOVED BEFORE iNSTALLATION BEFORE INBTALLATION...
  • Page 8 2,0'z,, FLUSH WITH SLAB_ _F2. 0- 4-1371 UNIT ROOF CURB BEE DETAIL NOTICE TO RIGGERS Hook rigging shackles through holes in lifting brackets, as shown in De- tail "A." Lifting brackets to be centered around the unit center of gravity. L.
  • Page 9 B. Units With Optional Base Rail Remove fl'om shipping location. Place vent cap assem bly over fine panel. Orient screw holes in vent cap with Lifting holes are provided in optional base rail as shown holes in the fine panel. Fig.
  • Page 10 Table I -- Physical Data -- Unit PYIP UNIT SIZE PYIP 018040 024040 024060 030040 030060 030080 036060 036080 036100 036120 11/2 2//z 2 Y, 2 i/, NOMINAL CAPACITY (ton) OPERATING WEIGHT (Ib) Without Base Rail With Optional Base Rail COMPRESSORS Rotary Reciprocating...
  • Page 11 A. Configuring Units for Downflow (Vertical) Discharge Open all electrical disconnects before starting any serv ice work. Remove return duct covet" located duct panel. Figure 12 shows duct covet" removed. Save duct cover screws. 3. Locate lances in basepan insulation that are placed over perimeter of the...
  • Page 12 Table 2 -- Maximum Gas Flow Capacity* NOMINAL INTERNAL LENGTH OF PIPE, FTI" IRON PIPE, DIAMETER SIZE (in.) (in.) .622 .824 1.049 11/4 1.380 1400 11/2 1.610 2100 !460 1180 *Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5-in. wg (based on a 0.60 specific gravity gas).
  • Page 13 X. STEP 10 -- INSTALL ELECTRICAL CONNECTIONS 1. Make all electrical connections in accordance with NEC ANSI/NFPA (latest edition) and local electrical codes gov Fig. 16 -- Vertical Discharge Cover Removed erning such wiring. In Canada, all electrical connec- tions must be in accordance with CSA standard...
  • Page 14 Table 3 -- Electrical Data -- Unit PYIP UNIT VOLTAGE AWG 60 C COMPRESSOR OUTDOOR-FAN INDOOR-FAN POWER SUPPLY MAX WIRE MOTOR MOTOR SIZE V-PH-Hz RANGE MIN WIRE LENGTH (ft) SIZE PY1P MOCP* 208/230-1-60 45.0 12.9 208/230-1-60 !2.4 6! .0 18.2 208/230-1-60 14.4 82.0...
  • Page 15 NOTE: Do not use any type of power stealing thermostat. Unit THERMOSTAT (TYPICAL) 1,¢o, ,¢,¢91 control problems may result. Use no. 18 American Wire Gage (AWG) color-coded, insu- lated (35 C mininmm) wires to make the control voltage con- t S J g, g nections between the thermostat...
  • Page 16 PRE-START-UP a. Before lighting the unit for the first time, perform the following: If the gas supply pipe was not purged before connecting the unit, it will be full of air. It is recommended that the ground joint union be loos- ened, and the supply line be allowed to purge...
  • Page 17 II. START UP HEATING SECTION AND MAKE C. Adjust Gas Input ADJUSTMENTS The gas input to the unit is determined by measuring gas flow at the meter or by measuring the manifold pressure. Measuring the gas flow at the meter is recommended for natu- ral gas units.
  • Page 18 Table 4 -- Rated Gas Inputs at Indicated Manifold Pressures GAS SUPPLY PRESSURE MANIFOLD NATURAL GAS PROPANE* NUMBER (in. wg) PRESSURE UNIT PY1 P Orifice (in, wg) Orifice Heating Heating Natural Propane ORIFICES Drill Drill Input Input Natural Propane Size Size (Btuh)t (Btuh)t...
  • Page 19 Table 5 -- Air Delivery (Cfm) at Indicated Temperature Rise and Rated Heating Input HEATING TEMPERATURE RISE °F INPUT (Btuh) 40,000 1389 1111 ..56,000 2083 1667 1389 1190 1042 ..80,000 2778 2222 1852 1587 1389 1235 1111 1010 ..
  • Page 20 III. START UP COOLING SECTION AND MAKE A superheat charging label is attached to the inside of the ADJUSTMENTS compressor access door. The label includes a "Superheat Charg- Table" a "Required Suction-Tube (F) Temperature" chart. An accurate superheat, thermocouple, or thermistor type ther monmter, a sling...
  • Page 21 VOLT OPERATION REVERSE REDAND GRN LEADSON TRANSFORMER. COOLING FAN LOGIC T+30 ENERGIZED DE'ENERGIZED RE_D RED_BRN HEATING LOGIC T÷3O ENERGIZED ENERGIZED I_'-Eh_R61ZED DE-ENERGIZED J_ I SINGLE STAGE HEAT _ 5Iit;LE STAGE COOL THERMOSTAT ¢TYP) )TRAN )ISCONNEO COMPONENT LEGEND Power American Wire Gage Btower ReIay Quadruple Terminal...
  • Page 22 MAXIMUM WIRE } ,_UP-I_,_Y-- --a_-,,--YEL S,ZE2 EQUIP 6ND 230 VOLT OPERATION A5 SHOWN. FOR 20B VOLT OPERATION REVERSE RED AND ORN LEADS ON TRANSFORMER. CO(_..INO FAN LOGIC BR I ..T+30 ENERGIZED DE-ENERGIZED HEATING FAN LOGIC T+30 ENERGIZED E NERGIZEO _ -ENEROIZED BE-ENERGIZED -- WHT' -- GRN -- RED...
  • Page 23 ,BLK BLK. BLK,_--- l CAP2 L?_-_p LBLU _---YELTL EQUIP GND BLI_ COMP BLK, J GH (036 & 042 ONLY) (G.E. COOLING FAN LOGIC T+3O ENERGIZED DE-ENERGIZED HEATING FAN LOGIC BRN-- T+3O ENERGIZED E NERGIZED I _E-ENERGIZEO OE-ENERGIZED _LU-------- --vIo _VIO-- _, t1-11-.
  • Page 24 Evaporator Airflow and Airflow Adjustments To change the speed of the blower motor, remove fan motor speed lead from the blower relay (BR) and replace with the lead for the desired blower motor speed. The motor speed lead is attached to terminal BM.
  • Page 25 Table 7A- Superheat Charging Table, PY1P018 INDOOR AIR -- CFM TEMP (F) OUTDOOR ENTERING Indoor Air -- Ewb (F) 17.3 !8.5 19.6 20.8 24.2 27.7 28.5 29.3 29.3 29.3 29.3 29.3 13.8 !4.9 16.1 !7.3 20.7 24.1 25.7 27.3 27.3 27.3 27.3 27.3...
  • Page 26 Table 7D -- Superheat Charging Table, PYIP036 INDOOR AIR -- CFM TEMP (F) 1200 OUTDOOR ENTERING Indoor Air -- Ewb (F) 12.5 16.7 18.7 20.7 22.0 23.4 24.8 26.1 13.! 15.9 18.6 20.0 21.3 22.7 24.0 13.! 16.6 17.9 19.3 20.6 22.0 10.3...
  • Page 27 Table 7G -- Superheat Charging Table, PYIP048 (Copeland Scroll Compressor) INDOOR AIR -- CFM TEMP (F) 1600 OUTDOOR ENTERING Indoor Air -- Ewb (F) 19.0 !9.0 19.0 !9.0 21.7 24.3 26.0 27.7 27.9 28.2 28.4 28.8 15.4 !5.4 15.4 !5.4 18.! 20.8 22.5...
  • Page 28 Table 8 -- Required Suction-Tube Temperature (F)* SUPERHEAT SUCTION PRESSURE AT SERVICE PORT (psig) TEMP (F) 61.6 64.2 67.1 70,0 73.0 76.0 79,2 82.4 86.7 *Temperature at su_ion service valve. Table 9 -- Dry-Coil Air Delivery* Horizontal Discharge at 230 and 460 V -- Unit PYIP (Deduct 10% from...
  • Page 29 Table 10 -- Dry-Coil Air Delivery* -- Downflow Discharge at 230 and 460 V -- Unit PYIP (Deduct 10% from Cfm and Watts for 208 V Operation) UNIT MOTOR EXTERNAL STATIC PRESSURE (in. wg) PYIP SPEED DELIVERY Watts Watts High !334 1253 1128...
  • Page 30 MAINTENANCE I. AIR FILTER To ensure continuing high performance, and to minimize possibility of premature equipment failure, periodic mainte- nance must be performed on this equipment. This combina tion heating/cooling unit should be inspected at least once each year by a qualified service person.
  • Page 31 c. Remove blower assembly fl'om unit. Remove screws securing blower to gas partition slide assembly out. carefld teal" insulation blower FLUE COLLECTOR compartment. Ensure proper reassembly by marking blower wheel INDUCED motor relation blower housing before DRAFT MOTOR disassembly. MOUNTING PLATE e.
  • Page 32 Remove ignitor sensor wires at the ignitor module. 7. Remove mounting screw that attaches burner rack to the basepan. (See Fig. 24.) Slide burner rack of the unit. (See Fig. 27.) 9. To reinstall, reverse procedure outlined above. ONkN_EOFTHU_PA_L BURNER ""_""_ACCESS PANEL Fig.
  • Page 33 X. CONDENSER NOTE: Refer to the heating and/or cooling sequence of op eration in this publication as an in determining proper control operation. XII. REFRIGERANT CIRCUIT Inspect all refrigerant tubing connections and the unit base 1. Remove 2 screws at bottom and 2 screws along sides of fox"...
  • Page 34 TROUBLESHOOTING Cooling SYMPTOM CAUSE REMEDY Compressor Power failure Call power company. condenser fan will Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker. not start. Defective thermostat, contactor, transformer, Replace component. or control relay Insufficient line voltage Determine cause and correct.
  • Page 35 Heating SYMPTOM CAUSE REMEDY Burners will not ignite. Water in gas line Drain. install drip leg. No power to furnace Check power supply fuses, wiring, or circuit breaker. Check transformer. No 24-v power supply to control circuit NOTE: Some transformers have internal overcurrent protection...
  • Page 36 LED Troubleshooting Error Code SYMPTOM CAUSE REMEDY Hardware failure. Loss of power to control module Check 5 amp fuse on IGC, power to unit, 24-v circuit (LED OFF) (IGC). breaker, and transformer. Units without a 24-v circuit breaker have an internal overload in the 24-v trans- former.
  • Page 37 PACKAGED SERVICE TRAINING Our packaged service training programs provide an excellent way to increase your kalowledge of the equipment discussed in this manual. Product progralns cover: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available. All pro m'ams include a video cassette and/or slides and a companion booklet.
  • Page 38 Copyright 1998 Payne Heating & Cooling CATALOG NO. 53PY-1P6...