Payne PA1P048 Installation & Start-Up Instructions page 9

Pa1p and pa2p single packaged electric cooling units
Table of Contents

Advertisement

UNiT SIZE
NOMINAL CAPACITY
(ton)
OPERATING
WEIGHT (lb.)
COMPRESSOR
REFRIGERANT
(R=22)
Quantity
(lb.)
REFRIGERANT
METERING
DEVICE
Orifice
ID {in.)
CONDENSER
COIL
Rows...Fins/in.
Face Area (sq, ft.)
CONDENSER
FAN
NominN
Cfm
Diameter
Motor Np (Rpm)
EVAPORATOR
COiL
Rows...Fins/in.
Face Area (sq, ft,)
EVAPORATOR
BLOWER
Nominal
Airflow
(Cfm)
Size (in.)
Motor Hp (RPN)
RETURN-AIR
FILTERS (in.)*
Throwaway
Required filter sizes shown are based on the larc
Table
1--Physical
Data--Unit
PAl P
018
024
042
048
0$0
1-1/2
2
3-1/2
4
5
254
260
294
324
389
Scroll
Reciprocating
2.6
3.5
6.4
5.1
7.4
.034
.034
.034
.032
.030
1...17
1...17
1...17
1...17
2...17
6.1
9.1
9.1
12.3
12.3
2000
2400
3000
3600
3600
22
22
22
22
22
1/8 (825)
1/8 (825)
1/4 (I100)
1/4 (I100)
1/4 (1100)
2._15
2...15
4...15
3._15
4._15
3.1
3.1
3.06
4.7
4.7
600
800
1400
1600
2000
10x10
10x10
11x10
11x10
11x10
1/4 (825)
1/4 (1075)
3/4 (I075)
3/4 (I075)
1.0 (1100)
20x20
20x20
20x24
24x30
24x30
er of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft./min
for throwaway type or 450 ft/min for high-capacity type Air filter pressure drop for non-standard filters must not exceed 008 in. wg.
030
036
2-1/2
3
258
268
Reciprocating
3.65
4.4
Accurater
.034
.032
1._17
1._17
9.1
10.9
2400
3000
22
18
1/8 (825)
1/4 (I100)
2...15
3...15
3.7
3.06
1000
1200
10x10
11x10
1/4 (1075)
1/2 (1075)
20x20
20x24
UNIT SIZE
NOMINAL
CAPACITY
(ton)
OPERATING
WEIGHT (lb.)
COMPRESSOR
REFRIGERANT
(R°22)
Quantity
(lb.)
REFRIGERANT
METERING
DEWCB
Orifice
ID (in.)
CONDENSER
COIL
Rows...Finsiin.
Face Area (sq. ft.)
CONDENSER
FAN
Nominal Cfm
Diameter
(in.)
Motor Np (Rpm)
EVAPORATOR
COIL
Rows...Finslin.
Face Area (sq. ft.)
EVAPORATOR
BLOWER
Nominal
Airflow
(Cfm)
Size (in.)
Motor Np (RPM)
RETURN-AIR
FILTERS (in.)*
Throwaway
Table
2--Physical
Data--Unit
PA2P
024
636
636
042
048
666
2
2-1/2
3
3-1/2
4
5
270
291
299
321
326
399
Scroll
3.7
4.4
5.2
7.6
8.3
8.1
Accurater
.034
.030
.032
.034
.034
.032
1._17
1...17
2._17
2...17
2...17
2._17
10.8
12.7
9.1
9.1
12.3
16.4
2350
2350
2350
3300
3300
3300
22
22
22
22
22
22
1/8 (825)
1/8 (825)
1/8 (825)
1/4 (1100)
1/4 (I100)
1/4 (1100)
3...15
3._15
3._15
3...15
4._15
4._15
3.1
3.1
3.7
4.7
4.7
4.7
800
1000
1200
1400
1600
1750
10x10
10x10
1lx10
1lx10
11x10
11x10
1/4
1/4
1/2
3/4
3/4
1.0 (1040)
1/4 (1075)
1/4 (1075)
1/2 (1075)
3/4 (1075)
3/4 (1075)
20x20
20x20
20x24
20x30
24x30
24x30
Required filter sizes shown are based on the larger of the ARI (Air Conditioning
and Refrigeration
Institute) rated cooling airflow or the heating airflow velocity of 300 ft./min
for throwaway
type or 450 ft/min
for high-capacity
type Air filter pressure drop for non-standard
filters must not exceed 008 in. wg.
1" (25mm) MIN.
TRAP
OBTLET
*,
2" (50ram) MIN.
Fig. 7--Condensate
Trap
C99013
12
Size all ductwork
%r maximum
required
airflow
(either
heating
or cooling)
%r unit being
installed,
Avoid
abropt
duct size increases
or
decreases
or performance
may be affected
9