Download Print this page

GE GTUN275GM1WW Installation Instructions Manual page 7

Unitized gas washer/dryer

Advertisement

Available languages

Available languages

Installation
Instructions
EXHAUST INFORMATION
(CONT)
27" DRYER EXHAUST LENGTH
RECOMMENDED M AXIMUMLENGTH
Exhaust Hood Types
Recommended
Use only for short
run installations
4 '1DIA.
I
I
Rigid
Metal
56 Feet
84 Feet
34 Feet
24 Feet
N o. of 90 °
Rigid
Elbows
Metal
0
82 Feet
1
32 Feet
2
25 Feet
3
18 Feet
24" DRYER EXHAUST LENGTH
RECOMMENDED
MAXIMUM
LENGTH
Exhaust Hood Types
Use ontg for short
run installations
4" DJA.
....... II-. _1_"
Recommended
Rigid.
Metal
45 Feet
33 Feet
28 Feet
No. of 90 °
Rigid.
Elbows
Hetal
0
36 Feet
1
26 Feet
2
16 Feet
EXHAUST SYSTEM CHECK LIST
HOOD OR WALL CAP
• Terminate in a manner to prevent back drafts or entry
of birds or other wildlife.
• Termination should present minimal resistance to
the exhaust air flow and should require little or no
maintenance to prevent clogging.
• Never install a screen in or over the exhaust duct. This
could cause lint build up.
• Wall caps must be installed at least 12 in. above
ground level or any other obstruction with the opening
pointed down.
SEPARATION OF TURNS
For best performance, separate all turns by at least
4 ft. of straight duct, including distance between last
turn and exhaust hood.
TURNS OTHERTHAN 90 °
• One turn of 45o or less may be ignored.
• Two 45 o turns should be treated as one 90 o turn.
• Each turn over 45 o should be treated as one 90 o turn.
SEALING OF JOINTS
• All joints should be tight to avoid leaks. The male end
of each section of duct must point away from the dryer.
• Do not assemble the ductwork with fasteners that
extend into the duct. They will serve as a collection
point for lint.
• Duct joints can be made air and moisture-tight by
wrapping the overlapped joints with duct tape.
• Horizontal runs should slope down toward the
outdoors 1/4 inch per foot
INSULATION
Duct work that runs through an unheated area or is
near air conditioning should be insulated to reduce
condensation and lint build-up.
I-]1 EXHAUST CONNECTION
iLWARNING
- TO REDUCE THE
RISK OF FIRE OR PERSONAL INJURY:
• This apliancce must be exhausted to the outdoors.
• Use only 4" rigid metal ducting for the home exhaust
duct.
• Use only 4" rigid metal or UL-listed flexible metal
(semi-rigid or foil-type) duct to connect the dryer
to the home exhaust duct. It must be installed
in accordance with the instructions found in
"Connecting The Dryer To House Vent" on page 8 of
this manual.
• Do not terminate exhaust in a chimney, a wall,
a ceiling, gas vent, crawl space, attic, under an
enclosed floor, or in any other concealed space
of a building. The accumulated lint could create a
potential fire hazard.
• Never terminate the exhaust into a common duct
with a kitchen exhaust system. A combination of
grease and lint creates a potential fire hazard.
• Do not use duct longer than specified in the exhaust
length table. Longer ducts can accumulate lint,
creating a potential fire hazard.
• Never install a screen in or over the exhaust duct. This
will cause lint to accumulate, creating a potential fire
hazard.
• Do not assemble ductwork with any fasteners
that extend into the duct. These fasteners can
accumulate lint, creating a potential fire hazard.
• Do not obstruct incoming or exhausted air.
• Provide an access for inspection and cleaning of
the exhaust system, especially at turns and joints.
Exhaust system shall be inspected and cleaned at
least once year.
THIS DRYER COMES READY FOR REAR
EXHAUSTING. IF SPACE IS LIMITED, USE
THE INSTRUCTIONS IN SECTION 9 TO
EXHAUST DIRECTLY FROM THE SIDES OR
BOTTOM OF THE CABINET.
EXTERNAL DUCT
OPENING
CSA (AGA} APPROVED
NEW FLEXIBLE
GAS
For straight
line installation,
connect
LINE CONNECTOR the dryer exhaust to the external
exhaust hood using duct tape or
GAS
clamp.
INLET
PIPE
DUCTTAPEOR
DUCTCLAMP
4" METALDUCTCUT
TO PROPER LENGTH
DUCTTAPEOR
DUCTCLAMP
7

Advertisement

loading

This manual is also suitable for:

Gtun275gm0wwGtup240gm5wwGtup270gm4ww