If necessary,
adjust the manifold
pressure
at the gas valve by removing
the regulator
cap and
turning the adjustment
screw clockwise
to raise the pressure
and counterclockwise
to reduce
the pressure.
The manifold
pressure
must be between 3.2" W.C. and 3.8" W.C. for natural gas
and 9.5"W.C.
and 10.5" W.C. for LP ( a field conversion
is necessary
for LP). The inability to
maintain the proper pressure
range will require reorificing.
After replacing
the orifices,
repeat
the above steps to insure that the furnace
input is adjusted
properly.
Turn off gas and electrical
supply, remove manometers
and replace any plugs which were
removed.
Use a pipe joint compound
which is suitable for use with LP gas.
Restore
any other appliances
affected to their normal operating
mode.
METER TIME IN MINUTES AND SECONDS FOR NORMAL INPUT RATING OF FURNACES EQUIPPED FOR USE
WITH NATURAL GAS AT 0 - 2,000 FEET ALTITUDE.
INPUT
Btu/hr
METER
SIZE
FT 3
HEAT
VAL UE
1,100
MIN. SEC.
HEAT
VALUE
900
MIN.
SEC.
1
21
13
30
0
54
9
00
0
41
6
45
0
32
5
24
0
27
4
30
HEAT
VAL U E
1,000
MIN.
SEC.
1
30
15
00
1
00
10
10
0
45
7
30
0
36
6
00
0
30
5
00
HEAT
VALUE
1040
MIN.
SEC.
1
33
15
36
1
O3
10
24
0
47
7
48
0
37
6
14
0
31
5
12
40,000
1
1
39
10
16
30
60,000
1
1
06
10
11
00
80,000
1
0
50
10
8
15
100,000
1
0
40
10
6
36
120,000
1
0
33
10
5
30
I
MAIN BURNER
ADJUSTMENT
The main burners should not need adjustment
in most instances.
However,
air shutters are
provided
should adjustment
be necessary.
After the furnace
has been in operation
for at least five (5) minutes
loosen the shutter locking
screw and close the shutter until yellow tipped flames appear.
Now slowly open the shutters until
the yellow disappears.
Retighten
the locking screw.
1
I
SAFETY
CONTROL
FUNCTIONS
AND CHECK-OUT
PROCEDURE
]
GENERAL
In most cases the safety controls
are wired is series with the "W" leg. It is imperative
that these
switches
remain in the circuit. Never jumper,
relocate (unless as noted on the furnace)
or bypass
any control. The safety controls
must be checked
for proper operation
at the time of start-up of
the furnace.
WARNING
I
SHOULD
ANY SAFETY
CONTROL
BE ALTERED,
JUMPERED
OR BYPASSED,
A
I
HAZARDOUS
CONDITION
SUCH AS FIRE OR THE POSSIBILITY
OF CARBON
MONOXIDE
I
ENTERING
THE BUILDING
MAY OCCUR.
I
IO-151