Nordyne E2 Series Owner's Manual & Installation Instructions page 19

Downflow, upflow electric furnaces air conditioner/heat pump air handler
Hide thumbs Also See for E2 Series:
Table of Contents

Advertisement

Model
Supply
E2EH/
E2EB-
Circuit
Amperes
010
Single
012
Single
Dual
"A"
"B"
015
Single
Dual
"A"
"B"
017
Single
Dual
"A"
"B"
020
Single
Dual
"A"
"B"
023
Single
Dual
"A"
"B"
* All wire sizes for copper conductors only, based on NEC Table 310-16. Equivalent wiring may be used per NEC.
Standard 2-Speed Blower,
with filter, @ 0.3" ESP
Pin No.
Speed
#1
Low
#2
High
4-Ton Blower with Coil and
Coil Filters, @ 0.3" ESP
Pin No.
Speed
#1
Low
#2
Med.-Low
#3
Med.-High
#4
High
5-Ton Blower, with Coil and
Coil Filters, @ 0.3" ESP
Pin No.
Speed
#1
Low
#2
Med.-Low
#3
Med.-High
#4
High
Table 7. Blower Performance
Max Over-
Min.
Total
Current
Circuit
Rating
Ampacity
60
57
45.5
70
65
52.1
40
35
28.0
30
30
24.2
90
83
66.3
60
57
45.5
30
26
20.8
90
89
71.3
60
61
48.8
22.5
30
28
125
109
87.1
60
57
45.5
60
52
41.7
125
117
93.8
60
57
45.5
60
60
48.3
Table 6. Electrical Specifications
CFM
840
1160
CFM
880
1170
1310
1460
CFM
990
1320
1620
1790
Sizes*
75°C Copper
Wire Size
Ground Size
6
10
6
8
8
10
10
10
4
8
6
10
10
10
3
8
6
10
10
10
2
6
6
10
6
10
1
6
6
10
6
10
Furnace
Model
Anticipator Setting
010, 012
015, 017,
020, 023
Table 8. Anticipator Settings
ALL MODELS
Front ‡
Back
Sides
Top
Top and Sides of Duct
Bottom of Duct
‡ Service Clearance
† For upflow application using upflow stand,
1" minimum per side.
Table 9. Clearances
Low-Voltage
Thermostat Wire
Size
2-Wire
system max
wire lengths :
24 Ga. = 55'
22 Ga. = 90'
20 Ga. = 140'
18 Ga. = 225'
4 or more-Wire
system max
wire lengths :
24 Ga. = 25'
22 Ga. = 45'
20 Ga. = 70'
18 Ga. = 110'
Thermostat
0.20
0.40
CLOSET
ALCOVE
6"
18"
0"
0"
0"†
0"†
0"
0"
0"
0"
0"
0"
19