Thermo Pride CHX3-75N Installation And Operation Manual page 48

Two stage condensing gas furnace
Table of Contents

Advertisement

All installations and services must be performed by qualified service personnel.
5. To obtain an accurate manifold gas pressure reading, the main burner must be cycled on and off
several times to stabilize the gas control valve pressure regulator diaphragm.
6. Allow the burner to operate for at least 3 minutes before taking gas pressure readings.
7. Using a pressure gauge, measure the burner manifold gas pressure.
8. If checking the input rate by measuring burner manifold pressure, skip to step 12. If
measuring the input rate using a gas meter, proceed to step 9.
9. Using a clock (or watch) capable of measuring time in seconds, carefully clock the gas meter to
determine the time for one (1) complete revolution of the gas meter dial or reel. At least one (1)
cubic foot of gas flow should be measured. Use Table 6 to determine the main burner gas flow
rate in cubic feet per hour (CFH).
NOTICE: Some gas meters will require more than one (1) cubic foot of gas pass through the
meter for reasons of accuracy. When more than one (1) cubic foot of gas is consumed, divide
the total time by the number of cubic feet for comparison to the figures in Table 6.
10. Compare actual heat input rate with our recommended input (printed on the furnace rating label).
To convert the rating label input rate (given in BTUH) to the equivalent gas flowrate (in CFH), use
the following formula:
Heat
input
rate
or,
Fuel
gas
flowrate
11. If the measured input rate is above, or below, the rating label value by more than 2%, adjust the
manifold gas pressure using the gas control valve pressure regulator to obtain the input rating
within a ± 2% range. Refer to steps 12(a) through 12(d).
12. If the gas pressure is not within the specified low fire manifold pressure range (refer to
Table 5), use the following procedure to adjust the low fire, gas pressure regulator to match the
specified low fire manifold pressure.
a. Remove the regulator cover screw from the gas valve. Refer to Figure 23.
=
(
in
BTUH
)
Fuel
gas
higher
heating
(
)
=
in
CFH
BTU
⎜ ⎜
⎟ ⎟
×
value
in
3
ft
Heat
input
rate
Fuel
gas
higher
heating
42
(
Fuel
gas
flowrate
in
(
in
BTUH
)
BTU
⎜ ⎜
⎟ ⎟
value
in
3
ft
)
CFH

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cdx3-75nChx3-100nCdx3-125nCdx3-100nChx3-125n

Table of Contents