A. Chimney Requirements
Measure vertical distances from the base of the fireplace
as shown in Figure 8.2.
Minimum overall straight height
Minimum height with offset/return
Maximum height
Maximum chimney length between an
offset and return
Maximum distance between chimney
stabilizers`
Double offset/return minimum height
Maximum unsupported chimney length
between the offset and return
Maximum unsupported chimney height
above the fireplace
Maximum unsupported chimney above
roof
WARNING! Risk of Fire! You must maintain 2 in. (51
mm) air space clearance to insulation and other combus-
tible materials around the chimney system. Failure to do
so may cause overheating and fire.
Table 8.1
HEIGHT OF CHIMNEy COMPONENTS
US
Canada ONLy
Chimney Stabilizer
SL11
Ceiling Firestops
FS538
FS540
Offsets/Returns
SL1130
Roof Flashing
RF570
RF571
Chimney Sections*
SL1106
SL1112
SL1118
SL1136
SL1148
n/a
* Dimensions reflect effective height.
ft
m
18
5.49
18.5
5.64
90
27.43
20
6.10
35
10.67
24
7.32
6
1.83
35
10.67
6
1.83
in.
mm
SL4
4-3/4
121
FS538
0
0
FS540
0
0
SL430
14-1/2
368
RF570
0
0
RF571
0
0
SL406
4-3/4
121
SL412
10-3/4
273
SL418
16-3/4
425
SL436
34-3/4
883
SL448
46-3/4
1187
SLA10
16-3/4
425
Heat & Glo • EXCLAIM-36, EXCLAIM-42 • 4013-251 Rev i• 3/12
Determine the chimney components needed to complete
your particular installation:
Measure the total vertical height of the fireplace
installation from the base of the fireplace assembly to
the approximate location of the bottom of the termination
cap.
Subtract the effective height of the fireplace assembly
(see Figure 8.2) from the total vertical height to determine
the overall height of the chimney installation.
Create a schematic for your application similar to Figure
8.2 showing components required (referring to Table
8.1). Figure 8.1 identifies those components and where
used.
Install a ceiling firestop whenever the chimney penetrates
a floor/ceiling.
NOTICE: A maximum of two pairs of offsets and returns
may be used.
CAUTION! Risk of Fire and/or Asphyxiation! DO
NOT connect this fireplace to a chimney flue servicing
another appliance. DO NOT connect to any air distribu-
tion duct or system. These actions could cause over-
heating/fire in the chimney flue, or release of exhaust
fumes into the living areas.
6 ft (1.8 m) max.
unsupported run
20 ft (6 m) max.
pipe between an
offset & return

Ceiling Firestop

11-10 in./279-254mm
adaptor required in
Canada
55-1/2 in.
(1410 mm)
Effective Height
(bottom of fireplace
to top of starter collar)
Figure 8.2

Chimney Requirements

6 ft (1.8 m) max.
unsupported chimney
above roof
35 ft (10.7 m)
max. straight
unsupported
chimney height
18.5 ft (5.6 m) min. height
single offset-return
24 ft. (7.3 m) min. height
double offset-return
90 ft (27.4 m) max. height