Clearances; Minimum Clearance - Heat & Glo EXCLAIM-36 Owner's Manual

Wood burning fireplace
Hide thumbs Also See for Heat & Glo EXCLAIM-36:
Table of Contents

Advertisement

B. Clearances
WARNING! Risk of Fire! You must comply with all minimum air space clearances to combustibles as specified in Fig-
ure 6.2. DO NOT pack required air spaces with insulation or other materials.
Figure 6.2
Storm Collar
Roof Flashing
(attic)
(insulation)
2 in. (51 mm) min.
Ceiling Firestop
48 in.
1219 mm
0 in.
to floor
Clearances to Combustible Materials
Note: Chimney air kit and 11-10 in./279-254 mm adapter are not shown,
but are required in Canada.
Heat & Glo • EXCLAIM-36, EXCLAIM-42 • 4013-251 Rev i• 3/12
Shaded areas
represent
2 in. (51 mm) min.
air space clearance
required around pipe
Attic
Insulation
Shield
(ceiling)
Offset/Return (secured
with hanger straps)
(ceiling)
Must have 2 in. (51 mm)

minimum clearance

to header
Adapter attached here (not shown)
0 in. to level
of standoffs
Clearance to back &
sides of appliance
Exclaim-36 - 1 in. (25 mm)
Exclaim-42 - 1 1/2 in. (38 mm)
(except at nailing flanges
where it is 1/2 in. [13 mm])