A. Chimney Requirements
Measure vertical distances from the base of the fireplace
as shown in Figure 8.2.
• Minimum overall straight height
• Minimum height with offset/return
• Maximum height
• Maximum chimney length between an offset and return
• Maximum distance between chimney stabilizers
• Double offset/return minimum height
• Maximum unsupported chimney length between the offset
and return
• Maximum unsupported chimney height above the
fireplace
• Maximum unsupported chimney above roof
WARNING! Risk of Fire! You must maintain 2 in. (51
mm) air space clearance to insulation and other combus-
tible materials around the chimney system. Failure to do
so may cause overheating and fire.
Table 8.1
HEIGHT OF CHIMNEY COMPONENTS
Chimney Stabilizer
SL3
Ceiling Firestops
FS338
FS339
FS340
Offsets/Returns
SL315
SL330
Roof Flashing
RF370
RF371
Chimney Sections*
SL306
SL312
SL318
SL324
SL336
SL348
* Dimensions reflect effective height.
13
(3.96 m)
14.5 ft
(4.42 m)
90 ft
(27.43 m)
20 ft
(6.1 m)
35 ft
(10.67 m)
20 ft
(6.1 m)
6 ft
(1.83 m)
35 ft
(10.67 m)
6 ft
(1.83 m)
in.
mm
4-3/4
121
0
0
0
0
0
0
13-3/8
340
15-1/2
394
0
0
0
0
4-3/4
121
10-3/4
273
16-3/4
425
22-3/4
578
34-3/4
883
46-3/4
1187
Heat & Glo • RH-36/RH-42 • 4044-153 • Rev AC • 1/11
Determine the chimney components needed to complete
your particular installation:
•
Measure the total vertical height of the fireplace
installation from the base of the fireplace assembly to
the approximate location of the bottom of the termination
cap.
•
Subtract the effective height of the fireplace assembly
(see Figure 8.2) from the total vertical height to determine
the overall height of the chimney installation.
•
Create a schematic for your application similar to Figure
8.2 showing components required (referring to Table
8.1). Figure 8.1 identifies those components and where
used.
•
Install a ceiling firestop whenever the chimney penetrates
a floor/ceiling.
NOTICE: A maximum of two pairs of offsets and returns
may be used.
CAUTION! Risk of Fire and/or Asphyxiation! DO
NOT connect this fireplace to a chimney flue servicing
another appliance. DO NOT connect to any air distribu-
tion duct or system. These actions could cause over-
heating/fire in the chimney flue, or release of exhaust
fumes into the living areas.
20 ft (6.10 m) max.
pipe between an
offset & return
Ceiling Firestop
39 1/2 in. (1003 mm)
Effective Height
Figure 8.2
Chimney Requirements
6 ft (1.83 m) max.
unsupported chimney
above roof
35 ft (10.67 m)
max. straight
unsupported
chimney height
14.5 ft (4.42 m) min. height/single offset-return
20 ft. (6.1 m) min. height/double offset-return
90 ft (27.43 m) max. height
25