GE VH Series 700 User Manual page 10

On-line vh series ups 700 - 1000 - 1500 - 2000 - 3000 va
Hide thumbs Also See for VH Series 700:
Table of Contents

Advertisement

3.3.4
Installation of a battery extension pack
With a battery extension pack you can increase the battery runtime of the UPS. If you do not install a battery
extension pack please skip this section and proceed with 3.3.5.
1
Before installation, check whether the
nominal voltage of the battery pack is
suitable for the UPS: the voltage
mentioned on the label on the battery
drawer of the UPS and the one on the rear
panel of the battery extension pack (36
Vdc or 72 Vdc) should match.
2.
UPS and battery pack can be mounted
together in one set of mounting supports.
3.
At the rear side the UPS and battery pack
can be coupled using the coupling bracket
that came with the battery pack.
4.
Connect the DC connector of the battery
pack to the DC socket of the UPS (4, fig.
3.3.3). You will hear a click when the cable
is properly connected. Block the DC
connector: install the small locking plate
that came with the battery pack, and
fasten it with the screw provided.
5.
Connect the DC connectors at the front
side of the battery pack (like in 3.3.1 step 4).
modifications reserved
OPM_VHE_XXX_0K7_3K0_XGB_V010
fig. 3.3.4a: installing battery extension pack(s) to the UPS
9
User manual VH Series 700-3000 UPS 1.0 (GB)
1
2
3
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents