Normal Operation; On Battery; Battery Low (End Of Runtime); Overload - GE VH Series 700 User Manual

On-line vh series ups 700 - 1000 - 1500 - 2000 - 3000 va
Hide thumbs Also See for VH Series 700:
Table of Contents

Advertisement

4.4.1
Standby
The UPS output is off, but the batteries are charging, see 3.3.6 step 5
4.4.2

Normal operation

See 4.3.1.
4.4.3
On bypass
The UPS is equipped with an automatic bypass switch. This switch automatically transfers the load to the
mains if the UPS is unable to deliver the demanded output power due to overload or overtemperature.
If all 4 load LEDs illuminate, bypass operation is caused by an overload. If only green load LEDs illuminate (the
red load LED is off), bypass operation is caused by overtemperature. Take appropriate measures: reduce load
and/or temperature.
The UPS will switch back to normal operation when the overload has been removed or the temperature has
dropped below alarm level.
If a power failure occurs during bypass operation, the UPS will switch to battery operation and eventually,
when the batteries are depleted, output power is lost.
The bypass function can be disabled - see 4.4.6 and 4.5 for further details.
Fail safe bypass operation: if the UPS becomes defective, the load may be switched to bypass (provided that
the bypass function was not disabled). As the status of the UPS is unknown in this situation the indications on
the operating panel may differ.
4.4.4

On battery

The UPS uses the energy stored in the batteries: see chapter 9 'Batteries - runtime'.
The runtime capacity LED bar will show the remaining runtime. The UPS will shutdown:
after the batteries have been discharged (automatic restart), or
if keypad 'O' is pressed (restart via front panel required) or
if a 'UPS shutdown' command is given by the computer. Restart depends on the setting of the 'auto
restart' function:
-
if set 'on' the UPS will automatically restart when the mains returns
-
if set 'off' a manual restart is required, either as in 4.2.1 step 1 or via the UPS management
software.
As default the 'auto restart' function is 'on'. The setting can be changed using the UPS monitoring software.
For more information please refer to the manual that came with the software.
4.4.5

Battery low (end of runtime)

If during 'on battery' operation the 25% LED starts blinking, the batteries are nearly discharged: the remaining
runtime is less than 2 minutes (default setting, adjustable via the UPS monitoring software). Controlled
shutdown of any computer equipment is absolutely necessary at this point.
If the UPS operates at 100% load, the shutdown procedure should be completed within 2 minutes after the
'battery low' alarm started. If only part of the output capacity of the UPS is used this period can be longer, with
aged batteries this period can be shorter.
When the batteries are fully discharged, the UPS is no longer able to power the connected equipment.
4.4.6
Bypass out of limits
The mains voltage or mains frequency are outside bypass input tolerance but inside UPS input tolerance (see
chapter 9). Bypass operation is inhibited: if for whatever reason the UPS is not able to deliver the required
output, output power is lost. If the input frequency is often out of tolerance – during which bypass operation is
inhibited and an alarm is generated – it may be useful to disable the bypass function after which the unit
operates as a UPS without automatic bypass switch. See 4.5.
modifications reserved
OPM_VHE_XXX_0K7_3K0_XGB_V010
15
User manual VH Series 700-3000 UPS 1.0 (GB)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents