American Standard ACONT900AC43UA Owner's Manual page 41

Communicating, programmable comfort control
Hide thumbs Also See for ACONT900AC43UA:
Table of Contents

Advertisement

American Standard Heating & Air Conditioning Droop is a feature that cycles the compressor on to
improve indoor comfort by removing moisture from the air. The Droop cycle is activated when the
indoor humidity is above the user's dehumidification setpoint.
Step 12. User Setup Number 0383: Dehumidification Maximum Droop.
To change Option, press the Up or Down arrow key to the right of the number in the lower right hand
corner of the screen. Options:
1 - 1° F (0.5° C)
2 - 2° F (1.0° C)
3 - 3° F (1.5° C)
Maximum droop is the amount of temperature overshoot allowed while attempting to control indoor
humidity.
Step 13. User Setup Number 0500: Furnace Air Filter Timer 1
To change Options, press the Up or Down arrow key to the right of the number in the lower right
corner of the screen. Options:
0 - Off. Furnace filter timer is off.
1 - 10 fan run time days (about one month).
2 - 30 fan run time days (about three months).
3 - 60 fan run time days (about six months).
4 - 90 fan run time days (about nine months).
5 - 120 fan run time days (about one year).
12-5046-02
41
69-1820—04