Emerson 1F95-1291 Installation And Operating Instructions Manual page 16

Big blue humidity universal thermostat with humidity/dehumidity control and automatic heat/cool changeover option single stage, multi-stage, heat pump
Table of Contents

Advertisement

TROUBLESHOOTING
Reset Operation
Note: If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the
thermostat by removing the thermostat from the wall plate and removing batteries for 2 minutes. After two minutes, replace
the batteries and replace thermostat on wall plate. If the thermostat has been reset and still does not function correctly contact
your heating/cooling service person or place of purchase.
Symptom
No Heat/No Cool/No Fan
(common problems)
No Heat
No Cool
Heat, Cool or Fan
Runs Constantly
Thermostat Setting &
Thermostat Thermometer
Disagree
Furnace (Air Conditioner)
Cycles Too Fast or Too Slow
(narrow or wide
temperature swing)
Forgot Keypad
Lockout Code
Blank display any or keypad
not responding
Thermostat does not have
Menu Screen Numbers
White-Rodgers is a business
of Emerson Electric Co.
The Emerson logo is a
trademark and service mark
of Emerson Electric Co.
Possible Cause
1. Blown fuse or tripped circuit breaker.
2. Furnace power switch to OFF.
3. Furnace blower compartment door or
panel loose or not properly installed.
4. Loose connection to thermostat or system.
1. Pilot light not lit.
2. Furnace Lock-Out Condition. Heat
may also be intermittent.
3. Heating system requires service or
thermostat requires replacement.
1. Cooling system requires service or
thermostat requires replacement.
1. Possible short in wiring.
2. Possible short in thermostat.
3. Possible short in heat/cool/fan system.
4. FAN Switch set to Fan ON.
1. Thermostat thermometer setting
requires adjustment.
1. The location of the thermostat and/or
the size of the Heating System may
be influencing the cycle rate.
1. Voltage Spike or static discharge
1. Earlier version of thermostat
HOMEOWNER HELP LINE: 1-800-284-2925
www.white-rodgers.com
www.emersonclimate.com
Corrective Action
Replace fuse or reset breaker.
Turn switch to ON.
Replace door panel in proper position to engage safety
interlock or door switch.
Tighten connections.
Re-light pilot.
Many furnaces have safety devices that shut down when
a lock-out condition occurs. If the heat works intermittently
contact the furnace manufacturer or local HVAC service
person for assistance.
Diagnostic: Set SYSTEM Switch to HEAT and raise the
setpoint above room temperature. Within a few seconds
the thermostat should make a soft click sound. This sound
usually indicates the thermostat is operating properly. If
the thermostat does not click, try the reset operation listed
above. If the thermostat does not click after being reset
contact your heating and cooling service person or place
of purchase for a replacement. If the thermostat clicks,
contact the furnace manufacturer or a HVAC service
person to verify the heating is operating correctly.
Same as diagnostic for No Heat condition except set the
thermostat to COOL and lower the setpoint below the
room temperature. There may be up to a five minute delay
before the thermostat clicks in Cooling.
Check each wire connection to verify they are not shorted
or touching together. No bare wire should stick out from
under terminal block. Try resetting the thermostat as de-
scribed above. If the condition persists the manufacturer
of your system or service person can instruct you on how
to test the Heat/Cool system for correct operation. If the
system operates correctly, replace the thermostat.
The thermometer can be adjusted +/- 4 degrees. See
Temperature Display Adjustment in the Configuration
Menu section.
Digital thermostats provide precise control and cycle
faster than older mechanical models. The system turns
on and off more frequently but runs for a shorter time
so there is no increase in energy use. If you would like
an increased cycle time, choose SL for slow cycle in the
Configuration menu, step 7 (heat) or 8 (cool). If an ac-
ceptable cycle rate is not achieved, contact a local HVAC
service person for additional suggestions.
key
key
Press the menu
(
will disappear) and hold in for
20 seconds. This unlocks the thermostat.
Use the Reset Operation shown above.
To access the earlier version instruction sheet (37-6914E)
go to www.white-rodgers.com, enter 1F95-1291 in Model
Number Search

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF