Optional Accessories; Section 3 - Post-Installation Start-Up Adjustments; Post Installation Tests; Before Initial Start-Up - Generac Power Systems PRIMEPACT 50 04164-3 Owner's Manual

Air-cooled recreational vehicle generators
Table of Contents

Advertisement

2.8.4
BATTERY COMPARTMENT
Install the generator battery in its own, vented compartment. Place
the battery compartment away from any source of heat, sparks
or flame.
Provide ventilation openings in the battery compartment. The
minimum size of openings should be 2 square inches at the top
of the compartment. Mount the battery on a strong, rigid support-
ing structure, where leaks and spills of battery fluid will not cause
damage.
2.9

OPTIONAL ACCESSORIES

A plug-in receptacle (Figure 2.21) is provided on the generator
set, above the muffler enclosure. Use this receptacle to connect
an optional remote-mounted start/stop panel to the generator.
Installation of such a panel will permit starting and stoping the
generator engine from any convenient location inside the vehicle.
Figure 2.21 – Remote Panel Plug-in Receptacle
2.9.1
REMOTE PANEL MODELS
The remote panels mount a rocker type start/stop switch, a
"Generator Run" advisory lamp and an hourmeter. The hourmeter
should be used in conjunction with the maintenance operations
found in Part I of this manual. The Prime switch is not connected,
it must be used with jumper wire 0G7666.
Model 0F0429 includes the remote panel and a 10 foot long,
5-wire harness.
Model 0F0430 includes the remote panel and a 30 foot long,
5-wire harness.
34
Section 3 – Post-installation Start-up Adjustments
Recreational Vehicle Generator
3.1

POST INSTALLATION TESTS

The air-cooled generator set was factory tested and adjusted. It
should not be required to adjust the unit any further except under
special circumstances.
Do not make any unnecessary adjustments.
Factory settings are correct for most applica-
tions. When making adjustments, however, be
careful to avoid overspeeding the engine.
3.2

BEFORE INITIAL START-UP

Before starting, complete the following:
1.
Check the engine crankcase oil level and, if necessary, fill to
the dipstick "FULL" mark (cross-hatched area) with the rec-
ommended oil. Do not fill above the FULL mark.
2.
Check the fuel supply. Gas fuel lines must have been properly
purged and leak tested in accordance with applicable fuel
codes. All fuel shutoff valves in the fuel supply lines must be
open.
DANGER
If a liquid propane (LP) gas fuel system has
been installed, it must be properly tested for
leaks before operating the system in compliance
with ANSI A119.2/NFPA 501C. No leakage is per-
mitted. Be sure no gasoline fuel vapors enter the
vehicle interior.
3.3

INITIAL START

When absolutely certain that the unit has been properly installed
and prepared for use, start the engine as follows:
1.
Turn off all electrical loads. Do this by setting the generator's
main circuit breakers to their "OFF" (or open) position.
2.
Refer to Part I, section "Starting the Generator", for cranking
and starting instructions. The engine may require more crank-
ing for initial starting since the fuel lines have to be primed
(use of the primer switch will shorten this time).
3.
Let the engine warm up for about five minutes to allow internal
temperatures to stabilize.
4.
Carefully inspect the engine/generator for fuel, oil and exhaust
system leaks. Before proceeding to the next step, correct any
leakage immediately.
5.
When all tests and adjustments at no-load are completed,
apply electrical loads and check for proper operation under
load. See the "Testing Under Load" section. Run the unit at
least 30 minutes with loads applied.
6.
Turn off all electrical loads by setting the generator's main
circuit breakers to their "OFF" (or OPEN) position.
7.
Let the unit run at no-load for a few minutes to stabilize
internal engine/-generator temperatures. Then, shut down the
engine.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Primepact 50 05754-0Primepact 50lp 04164-3

Table of Contents