Finding the Power Supply Module Serial Number

Connect the DC-input power terminals to the terminal blocks. See
Step 3
to match the polarity (negative to negative, positive to positive) when connecting the wires to the
terminal blocks. Connect the ground wire to a grounded metal rack or to earth ground if the switch is not
in a grounded rack.
Figure 4-12
Figure 4-13
Torque all terminal block screws to 11 lbf-in.
Step 4
Replace the terminal block safety cover.
Step 5
Move the DC power source circuit-breakers to the ON position.
Step 6
Confirm that the power supply DC OK and PS OK LEDs are green. See
Step 7
the module LEDs.

Finding the Power Supply Module Serial Number

If you contact Cisco Technical Assistance regarding a power supply module, you need to know the serial
number. See
the serial number.
Catalyst 3850 Switch Hardware Installation Guide
4-12