Table 59. Status Tables.
Name
CH
DHW
Burner Control
Demand and Modulation
Inlet High Limit
Fan
Pump
Flame Detection
Statistics
Stack Limit
Lead Lag Slave
Lead Lag Master
Parameters
A complete list of configurable parameters is shown in Table
60.
Table 60. Configurable Parameters.
Parameter
Comment
Boiler Name Name to identify boiler (up to 20
characters)
Installation
Notes regarding installation (up
to 20 characters)
Installer
Change installer password
password
setting
OEM
Change OEM password setting
password
Factory Data OEM name to associate with
boiler (up to 20 characters)
65-0315—02
Table #
Page #
44
30
45
31
46
32
47
33
48
33
49
33
50
34
51
34
52
34
53
35
54
35
55
35
Table
Page
#
#
5
14
42
Table 60. Configurable Parameters. (Continued)
Parameter
Comment
CH enable
Disable or Enable Central
Heating Loop
CH demand
Sensor for Central Heat
switch
demand:
Sensor only
Sensor & STAT terminal
Sensor & Remote Stat
LCI & Sensor
CH Outdoor
Enabled
reset
Disabled
CH has
Yes, No, Cancel
priority over
Lead Lag
CH Setpoint
Local
source
S2 (J8-6) 4-20mA
CH Setpoint
Setpoint for normal Central
Heat modulation:
-40 °F to 266 °F
(-40 °C to 130 °C)
CH time of
Setpoint when Time Of Day
day setpoint
switch is on. -40 °F to 266 °F
(-40 °C to 130 °C)
CH off
Differential above setpoint
hysteresis
when boiler is turned off. -40 °F
to 266 °F (-40 °C to 130 °C)
CH on
Differential from setpoint when
hysteresis
boiler is turned on.-40 °F to 266
°F (-40 °C to 130 °C)
4 mA water
-40 °F to 266 °F
temperature
(-40 °C to 130 °C)
20 mA water
-40 °F to 266 °F
temperature
(-40 °C to 130 °C)
Modulation
Outlet sensor, Inlet sensor, S5
sensor
(J8-11)
Modulation
Local
Rate Sensor
CH P-gain
Time between hysteresis step
changes: 0-400
CH I-gain
Time between hysteresis step
changes: 0-400
CH D-gain
Time between hysteresis step
changes: 0-400
Hysteresis
Time between hysteresis step
step time
changes: 0-600 seconds
(0=Disable hysteresis stepping)