Table 8. Steam Configuration Parameters
Parameter
Steam enable
Disable/enable steam feature
Steam demand
Sensor and LCI
source
Sensor and Remote Stat
Sensor and Stat Terminal
Sensor Only
Steam pressure
Setpoint for normal modulation
setpoint
Adjustable 0 to 15 or 0 to 150 (sensor
dependant)
Steam time of day
Setpoint when TOD switch on
setpoint
Adjustable 0 to 15 or 0 to 150 (sensor
dependant)
Minimum steam
Establishes setpoint for the 4ma. input.
pressure
Adjustable 0 to 15 or 0 to 150 (sensor
dependant)
Steam pressure off
Differential below setpoint when boiler
hysteresis
is turned off
Adjustable 0 to 15 or 0 to 150 (sensor
dependant)
Steam pressure on
Differential from setpoint when boiler
hysteresis
is turned on.
Adjustable 0 to 15 or 0 to 150 (sensor
dependant)
Steam hysteresis
Time between hysteresis changes 0 to
step time
600 seconds (0=disable)
Steam P Gain
Gain applied for the P portion of the
PID equation
0-400
Steam I Gain
Gain applied for the I portion of the PID
Equation - 0-400
Steam D Gain
Gain applied for the D portion of the
PID equation
0-400
Steam 4-20 ma
uses 4-20ma remote control function to
remote control
control either the setpoint or
modulation for Steam
Disable, setpoint, modulation
Outdoor Reset Parameters
(R7910 Hydronic Control Only)
Table 9 displays Outdoor Reset configuration parameters.
Pressing the left or right arrow displays Lead Lag, which lists
the same parameters.
65-0315—02
Comment
16
Fig. 32. Outdoor reset configuration.
Table 9. Outdoor Reset Configuration Parameters.
Parameter
Maximum outdoor
-40 °F to 266 °F (-40 °C to 130 °C)
temperature
Minimum outdoor
-40 °F to 266 °F (-40 °C to 130 °C)
temperature
Low water
-40 °F to 266 °F (-40 °C to 130 °C)
temperature
Minimum water
-40 °F to 266 °F (-40 °C to 130 °C)
temperature
Maximum off point
-40 °F to 266 °F (-40 °C to 130 °C)
Domestic Hot Water (DHW)
Configuration Parameters
(R7910 Hydronic Control Only)
Table 10 displays Domestic Hot Water (DHW) configuration
parameters.
Fig. 33. Domestic Hot Water (DHW) configuration.