Table 10. Domestic Hot Water (DHW)
Configuration Parameters.
Parameter
Enable
Disable or Enable Domestic Hot Water
Loop
Demand switch
Sensor for Central Heat demand:
DHW sensor only,
DHW sensor & Remote Stat,
DHW switch & inlet sensor, or
DHW switch & outlet sensor
Priority source
Which system has priority:
Disabled or
Heat Demand
Priority method
Boost during priority time
Drop after priority time
Modulation sensor
DHW Sensor
Outlet Sensor
Inlet Sensor
Auto: DHW (S6) or Inlet Sensor
Auto: DHW (S6) or Outlet Sensor
Setpoint
-40 °F to 240 °F (-40 °C to 115 °C)
Time of day setpoint Setpoint when Time Of Day switch is
on. -40 °F to 240 °F (-40 °C to 115 °C)
Off hysteresis
Differential above setpoint when boiler
is turned off. -40 °F to 240 °F (-40 °C
to 115 °C)
On hysteresis
Differential from setpoint when boiler
is turned on.
2 °F to 234 °F (-16 °C to 112 °C)
DHW priority
___hour ___min ___sec
override time
Hysteresis step
___hour ___min ___sec
time
DHW priority vs CH Which system has priority:
Central Heat over Domestic Hot
Water, or
Domestic Hot Water over Central Heat
DHW priority vs
Which system has priority:
Lead Lag
Lead Lag over Domestic Hot Water,
Domestic Hot Water over Lead Lag
DHW P-gain
Gain applied for the P portion of the
PID equation
0-400
DHW I-gain
Gain applied for the I portion of the
PID equation
0-400
DHW D-gain
Gain applied for the D portion of the
PID equation
0-400
Comment
DHW Storage Configuration
Table 11 displays DHW Storage configuration parameters.
Table 11. DHW Storage Configuration Parameters.
Parameter
DHW storage
Enabled, Disabled
enable
Storage time
___hour ___min ___sec
Setpoint
32 °F to 250 °F (0 °C to 120 °C)
Off hysteresis
0 °F to 234 °F (-17 °C to 112 °C)
On hysteresis
0 °F to 234 °F (-17 °C to 112 °C)
DHW Plate Heat Exchanger
Configuration
Table 12 displays DHW Plate Heat Exchanger configuration
parameters.
Table 12. DHW Plate Heat Exchanger
Configuration Parameters.
Parameter
Tap detect degrees -0 °F to 180 °F (-17 °C to 82 °C)
Tap detect on
___hour ___min ___sec
recognition time
Tap detect on
-0 °F to 180 °F (-17 °C to 82 °C)
threshold
Tap detect minimum
___hour ___min ___sec
on time
Tap stop inlet-DHW
-0 °F to 180 °F (-17 °C to 82 °C)
degrees
Tap stop outlet-Inlet
-0 °F to 180 °F (-17 °C to 82 °C)
degrees
Plate preheat
-40 °F to 266 °F (-40 °C to 130 °C)
setpoint
Plate preheat on
___hour ___min ___sec
recognition time
Plate preheat on
-0 °F to 180 °F (-17 °C to 82 °C)
hysteresis
Plate preheat off
-0 °F to 180 °F (-17 °C to 82 °C)
hysteresis
Plate preheat detect
-0 °F to 180 °F (-17 °C to 82 °C)
on threshold
Plate preheat detect
-0 °F to 180 °F (-17 °C to 82 °C)
off threshold
Plate preheat
___hour ___min ___sec
minimum on time
Plate preheat delay
___hour ___min ___sec
after tap
17
Comment
Comment
65-0315—02