Download Print this page

Special Features - Tripp Lite SU10000RT3U2TF Specifications

Smartonline 10kva on-line double-conversion ups, 10u rack/tower, 208/120v nema outlets
Hide thumbs Also See for SU10000RT3U2TF:

Advertisement

Relative Humidity
0 to 95%, non-condensing
AC mode BTU / hr.
3415
(full load)
AC economy mode
1275
BTU / hr. (full load)
AC economy mode
96%
efficiency rating
(100% load)
Operating Elevation
0-3000m (0 to 10,000 ft.)
(ft.)
Audible Noise
60 dBA at front side 1 meter
Operating Elevation
0-3000 m
(m)
COMMUNICATIONS
Communications
USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
interface
Network monitoring
Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI
port description
installation requires removal of panel containing USB ports
PowerAlert software
Included
Communications
USB, DB9 serial and EPO cables included
cable
WatchDog
Supports Watchdog application, OS and hard-reboot restart options for remote applications
compatibility
LINE / BATTERY TRANSFER
Transfer time
No transfer time (0 ms.) in online, double-conversion mode
Transfer time
8 ms. typical power failure response in optional economy mode
(economy mode)
Low voltage transfer
100V
to battery power
(setpoint)
High voltage transfer
300V
to battery power
(setpoint)

SPECIAL FEATURES

Cold Start (startup in
Cold-start operation supported
battery mode during
a power failure)
Economy mode
Optional economy mode enables high efficiency bypass operation with a maximum output voltage variation of
operation
+/-10%. Double conversion mode is automatically restored as mains voltage varies beyond +/-10% with less than 1
millisecond transfer time between modes.
High availability UPS
Automatic inverter bypass; Manual bypass switch; Detachable hot-swap PDU; Hot swappable UPS power module;
features
Hot swappable batteries
Green & high
High efficiency economy mode operation; Schedulable daily hours of economy mode operation
efficiency features
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
UPS Certification
IEC 61000-4-5 1995 B Surge Immunity
details

Advertisement

loading