Download Print this page

Special Features - Tripp Lite SU80KX Specifications

Smartonline 80kva modular 3-phase ups system, on-line double-conversion international ups
Hide thumbs Also See for SU80KX:

Advertisement

UPS / Power Module
116.8 x 52.1 x 85.6
dimensions in
primary form factor
(height x width x
depth / cm)
Installed whole
0
system maximum
rack depth (cm)
UPS / Power Module
538
weight (lbs)
UPS / Power Module
244.3
weight (kg)
UPS Shipping
55 x 28.5 x 42.5
dimensions (height x
width x depth / inches)
UPS Shipping
139.7 x 72.4 x 108
dimensions (height x
width x depth / cm)
Shipping weight (lbs)
687.8
Shipping weight (kg)
312.3
Cooling method
Fans
UPS housing material
Steel
ENVIRONMENTAL
Operating
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Temperature Range
Storage Temperature
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Range
Relative Humidity
0 to 95%, non-condensing
COMMUNICATIONS
Communications
DB9 Serial; Slot for SNMP/Web interface
interface
PowerAlert software
Included
Communications
DB9 cabling included
cable
LINE / BATTERY TRANSFER
Transfer time
No transfer time (0 ms.) in online, double-conversion mode
Low voltage transfer
Maintains continuous operation without using battery power during brownout/undervoltage conditions to 173-300V
to battery power
AC (3-phase, 4-wire, wye). Below this point, output is maintained utilizing reserve battery power
(setpoint)
High voltage transfer
Maintains continuous operation without using battery power during overvoltages to 276-477V AC (3-phase, 4-wire,
to battery power
wye), reducing output within 1% of nominal. Above this point, output is maintained utilizing reserve battery power
(setpoint)

SPECIAL FEATURES

Cold Start (startup in
Cold-start operation supported
battery mode during a
power failure)
High availability UPS
Automatic inverter bypass; Hot swappable batteries
features

Advertisement