HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
7/07

Table 14 Relay Type Descriptions

The Relay can be set up to indicate ...
The upper / lower limits of the input signal have been exceeded.
Relay value parameter defines range limits and units are in percent of full span.
Upper / lower limits of motor position have been exceeded.
Relay value parameter defines range limits and units are in either percent of
span or degrees of rotation. See "Relay Examples "for setting range limits.
Motor position has exceeded deviation limit from input. (Deviation is defined as:
setpoint – motor position = Deviation)
Relay value parameter defines limits and units are in percent of span.
See "Relay Examples" for setting deviation limit.
The motor position has exceeded the upper limit of travel.
(Same as Position Range.)
Relay value parameter defines limits and units are in degrees of rotation or
percent of span. See "Relay Examples" for setting upper limit with hysteresis.
The motor position has exceeded the lower limit of travel.
(Same as Position Range.)
Relay value parameter defines limits and units are in degrees of rotation or
percent of span.
The high temperature limit of the actuator has been exceeded. Relay value
parameter defines temperature limits and units are in either degrees C or
degrees F.
(Temperature units are defined in the UNITS setting of the DISPLA set up
group.)
The low temperature limit of the actuator has been exceeded. Relay value
parameter defines temperature limits and units are in either degrees C or
degrees F.
(Temperature units are defined in the UNITS setting of the DISPLA set up
group.)
The accumulated motor starts have exceeded the limit. Relay value parameter
defines the limit. See "Relay Examples" for setting motor starts limit. Range is
from 10 to 99,990,000.
The motor is in a stall condition.
The actuator is in manual mode.
A failure of any one of the power up test diagnostics. See READ STATUS set up
group.
The actuator is in failsafe. (input signal loss or input signal out of valid range)
The potentiometer or non-contact sensor output is out of range or has failed.
The digital input closure.
The total degrees traveled.
Set Up and Calibration Procedures
Relays Set Up Group
45