Start-up
Press the configuration button (1) repeatedly until the last LED goes
out.
The storey controller is back in normal mode.
If the configuration button is not pressed for longer than three
minutes, the storey controller changes to normal mode. The
assigned temperature zones remain stored in the storey
controller, even after a power failure.
Assigning setpoint adjusters of type HCU 23 or HCW 23 to
a zone
Setpoint adjusters and room sensors are assigned (fixed) to the
temperature zones due to their wiring. Refer to "Connecting setpoint
adjusters HCU 23 and HCW 23" on Page 28.
If the setpoint adjuster and room sensor are removed, the
assignment must be removed as well. See "Removing
assignment".

Removing assignment

Removing temperature zone on HCE 40
If you would like to remove a temperature zone, e.g. if it was assigned
accidentally or a setpoint adjuster has been uninstalled and is no
longer required, proceed as follows: