Herculine 2000 Terminal Connections; Table 3 Terminal Connections: Herculine ® 2000; Table 4 Terminal Connections: Herculine; Figure 1 Herculine - Honeywell 2000 Series Installation, Operation And Maintenance Manual

Herculine 2000 series
Hide thumbs Also See for 2000 Series:
Table of Contents

Advertisement

Installation
Electrical Installation
®
HercuLine
2000 Terminal Connections
Connection
Hot
Neutral
Auto/Manual Switch
Contact
CW from Controller
CCW from Controller
Potentiometer #1
Potentiometer #2
Protective Ground
158 ohm
158 ohm
18
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
Table 3 Terminal Connections: HercuLine
Terminal Numbers
and LABEL
See Figure 8
1
Hot wire for 120/240VAC mains supply. Use only if Auto/Manual
switch is present.
2
Neutral wire for 120/240VAC mains supply
3
Switch contact to indicate setting of actuator AUTO/MANUAL
4
switch.
Switch is closed when actuator is "NOT-IN-AUTO"
5
CW motor drive
6
CCW motor drive
7
Clockwise-End
8
Slider
9
Counterclockwise-End
10
Clockwise-End
11
Slider
12
Counterclockwise-End
Ground wire connection for mains supply
158 ohm
158 ohm
Install resistors to convert 1000 ohm
Install resistors to convert 1000 ohm
potentiometer to 135 ohms
potentiometer to 135 ohms

Figure 8 HercuLine

®
2000
Descriptions
1 1
1
REQUIRED ONLY IF AUTO/MANUAL
REQUIRED ONLY IF AUTO/MANUAL
1 1
1
SWITCH IS PRESENT
SWITCH IS PRESENT
®
2000 connections
Revision 6
7/07

Advertisement

Table of Contents
loading

Table of Contents