Because these temperatures might be significantly higher than the temperatures of the other
equipment in the data center, to not over-cool the air, you might have to adjust the set-points of
the CRACs or CRAHs higher. Most standalone CRACs and CRAHs use return side temperature
regulation rather than supply side. Since the supply side air temperature is the parameter of interest
to meet the 15-32 °C limits for the proper operation of Superdome2, you might have to increase
the return air set-points to maximize the capacity of the CRACs or CRAHs.
IMPORTANT:
you do not exceed the actual inlet temperature specified for any equipment.
For more information about general site preparation guidelines, see the Generic Site Preparation
Guide.

Air quality specifications

Chemical contaminant levels in customer environments for HP hardware products must not exceed
G1 (mild) levels of Group A chemicals at any time, as described in the current version of ISA–71.04
Environmental Conditions for Process Measurement and Control Systems: Airborne Contaminants.
See
http://www.isa.org/
For more information about general site preparation guidelines, see the Generic Site Preparation
Guide.

Acoustic noise specifications

The acoustic noise specifications are 8.6 bel (86 dB) (sound power level).
IMPORTANT:
periods of time wear hearing protection or use other means to reduce noise exposure.
This level of noise is appropriate for dedicated computer room environments, not office environments.
When adjusting the set-point of any CRAC or CRAH, you must be careful so that
for more information.
HP recommends that anyone in the immediate vicinity of the product for extended
Environmental specifications