Current Draw And Thermal Dissipation Specifications - Lab.gruppen FP14000 Operation Manual

Dedicated touring amplifiers fp+ series
Hide thumbs Also See for FP14000:
Table of Contents

Advertisement

8 APPENDIX
8.4

Current draw and Thermal dissipation specifications

The following tables contain information on measured current consumption as well as calculated heat dissipation during normal operation
The following tables contain information on measured current consumption as well as calculated heat dissipa-
(1/8 rated power); and during extreme heavy duty operation (max power).
tion during normal operation(1/8 rated power); and during extreme heavy duty operation (1/4 rated power).
Level
Load
Standby with remote power off via Nomadlink
Power on, Idling
Pink noise
16 Ω / Ch.
(1/8th rated
32 Ω / Bridged
power)
8 Ω / Ch.
16 Ω / Bridged
4 Ω / Ch.
8 Ω / Bridged
2 Ω / Ch. *4)
4 Ω / Bridged *4)
Pink noise
16 Ω / Ch.
(max power)
32 Ω / Bridged
*3)
8 Ω / Ch.
16 Ω / Bridged
4 Ω / Ch.
8 Ω / Bridged
2 Ω / Ch.
4 Ω / Bridged
Mains connector, 230 V CE version
Mains connector, 115 V ETL version
*1) The amplifi er's PSU operates as a non-resistive load, so the calculation "Volts x Amps = Watts" would not be correct. Instead, measured and specifi ed here
is what is known as the "Active Power" of the amplifi er providing useful, real-world values of power consumption and heat dissipation.
*2) Current draw fi gures measured at 230 V. 115 V fi gures are 230 V fi gures multiplied by two.
*3) Figures measured at maximum sustainable power without tripping the mains fuse. Listed separately for 30 A/115 V and 16 A/230 V operation . Note that
the max. power condition is very extreme and will not occur during normal operation. Also note that the mains breaker will not be tripped even if operation is
momentarily in excess of max. ratings.
*4) Italics used for conditions that, if sustained over long time periods, may trigger the mains breaker. Therefore these measurements should not be used when
calculating cooling requirements as they cannot be sustained by the mains breaker over time.
Table 8.4a: FP 14000 Current Draw and Thermal Dissipation specifications
28 FP+ Series Operation Manual
FP 14000
Rated power
Line Current *2)
120 VAC
230 VAC
®
Amp (I)
1200
x 2
9.1
4.8
2400
x 1
2350
x 2
14.8
4700
x 1
4400
x 2
23.9
12.5
8800
x 1
7000
x 2
34.0
17.8
14000
x 1
1200
x 2
16.0
8.4
2400
x 1
2350
x 2
30.0
16.0
4700
x 1
4400
x 2
30.0
16.0
8800
x 1
7000
x 2
30.0
16.0
14000
x 1
16 A, CEE7
30 A, Twist lock
Watt *1)
In
Out
0
0
122
0
Watt
628
300
7.7
1081
588
1880
1100
2750
1750
1253
800
2259 / 2409
1500 / 1600
2320 / 2474
1463 / 1560
2277 / 2429
1266 / 1350
Thermal dissipation
Dissipated
BTU/hr
kCal/hr
0
0
0
122
416
105
328
1118
282
493
1683
424
780
2661
670
1000
3412
860
453
1546
390
759 / 809
2589 / 2762
652 / 696
857 / 914
2926 / 3121
737 / 786
1012 / 1079
3453 / 3683
870 / 928