W7212, W7213, W7214 ECONOMIZER LOGIC MODULES

SPECIFICATIONS

Models: W7212A, W7213A, W7214A Logic Modules: for use
with any Honeywell 2-10 Vdc actuator; includes DCV
(CO2) input; adjustable exhaust fan setpoint.
NOTES:
All models include a minimum damper position
potentiometer, and setpoints for: enthalpy or
dry-bulb, occupied/unoccupied control, DCV
(CO2) operation, CO2 sensor failure mode and
DCV maximum (DCV MAX).
Occupied/Unoccupied overrides minimum
damper position setting when building is
unoccupied.
On CO2 sensor failure the damper outdoor
damper defaults to DCV maximum position. See
table 1 for economizer functions based on occu-
pancy, CO2 input and damper positions for
adjustments of potentiometers for MIN POS and
DCV MAX. This feature was added with series 2
version of the product; series 1 does NOT default
to DCV MAX, series 1 defaults to MIN POS on
failure of CO2 sensor.
Dimensions: See Fig. 1.
Electrical Ratings:
Input Voltage: 24 Vac ±20%; 50/60 Hz (Class 2).

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2596—09
Nominal Power Consumption (at 24 Vac, 60 Hz): 11.5 VA.
Relay Contact Rating at 30 Vac (maximum power from class 2
input only): 1.5A run, 3.5A inrush.
IMPORTANT
All inputs and outputs must be 24 Vac Class 2.
Ambient Ratings:
Temperature: -40°F to +149°F (-40°C to +65°C).
Humidity: 5 to 95 percent RH (noncondensing).
Inputs:
Enthalpy (C7400): 2-wire (18,20,22 AWG) connection.
Dry Bulb Temperature (C7660): 2-wire (18,20,22 AWG)
connection.
Discharge Air (C7046): 2-wire (18,20,22 AWG) connection.
Mixed Air (C7150): 2-wire (18,20,22 AWG) connection.
DCV (CO2) Sensor (C7232): 0/2-10 Vdc control signal;
100K ohm input impedance.
Outputs:
Actuator Signal: 2-10 Vdc.
Minimum Actuator Impedance: 1K ohm.
Exhaust Fan: Contact closure.
24 Vac Out: 25 VA maximum.