Download Print this page

Honeywell 5 Nm Series Product Data page 5

Non-spring return direct-coupled damper actuators for floating and two-position control

Advertisement

END SWITCHES (CLASS II-ONLY)
S1
S2
S3
Fig. 9. End Switches.
NOTE: Both internal end switches must be connected to the
same power source.
Tables 2 and 3 summarize the information presented in the
preceding wiring diagrams.
Typical Wiring With Cables
Fig. 10. MN6105W1011 Two Position/Floating.
85°
S5
S6
M23110
ACTUATOR
1
V
2
BLK
OR +
3
RED
POS 50%
4
WHT
5
FEEDBACK
Dir
Service/Off
Rev
M28933
Table 2. Signals at Terminals from MN6105/MN6110.
Terminal
Signal in Floating
2
Common ~/-
3
24 V ~/-
(control signal)
4
24 V ~/-
(control signal)
NOTE: All cables connected to these terminals must be
equipped with spark suppression.
Table 3. Internal End Switches.
Terminal
S1
Common lead for switches A and B.
S2/S3
Change-over switch A (S1/S2 opens and S1/S3
closes when shaft adapter moves CC past 5°;
reverts to original state when shaft adapter moves
CCW past 5°).
S5/S6
Change-over switch B (S1/S6 closes when shaft
adapter moves CW past 85°; reverts to original
state when shaft adapter moves CCW past 85°).
5
5 NM, 10 NM SERIES
Signal in 2-Pos. Mode
Common ~/-
24 V ~/-
(control/power signal)
24 V ~/-
(control/power signal)
Type of Switch
63-2632—03

Advertisement

loading

This manual is also suitable for:

Mn6105Mn6110