Ignition Delay; Adjusting The 3.6.7. Soft Lighta - Ariston ecoCOMBI 27 MFFI Installation And Servicing Instructions

Microcondens series, type c boilers
Hide thumbs Also See for ecoCOMBI 27 MFFI:
Table of Contents

Advertisement

F
. 3.13
IG
C
D
E
F
. 3.14
IG
3.6.5 I
D
A
GNITION
ELAY
The ignition delay can be adjusted to between 0 and 15 minutes. The delay is factory
set to 2 minutes.
The value set can be displayed as illustrated in paragraph 3.6.2.
To access the potentiometer "C" (Fig. 3.14), open the control panel as illustrated in
paragraph 3.2 and open up the service flap (Fig. 3.13).
3.6.6 A
M
DJUSTING THE
The maximum heating power can be adjusted to between the maximum power
allowed by the boiler (24 kW) and the minimum one (8 kW). The value is factory set to
70% of the maximum power.
The value set (expressed as a percentage) can be displayed as illustrated in
paragraph 3.6.2.
To access the potentiometer "D" (Fig. 3.14), open the control panel as illustrated in
paragraph 3.1 and open up the service flap (Fig. 3.13).
The display shows the value between 100% ("00" on the display) and 1% ("01") of this
interval.
kW
25
20
15
Heat
input
10
5
0
0
10
3.6.7 S
L
A
OFT
IGHT
DJUSTMENT
The soft light can be adjusted between the maximum power (shown on the display as
"00", i.e. 100%) and minimum power (shown on the display as "01", i.e. 1%). The
boiler is factory set to a value which is suitable for ignition with any type of gas
(approx. 33%).
The value set (expressed as a percentage) can be displayed as illustrated in
paragraph 3.6.2.
To access the potentiometer "E" (Fig. 3.14), open the control panel as illustrated in
paragraph 3.1 and open up the service flap (Fig. 3.13).
DJUSTMENT
H
P
AXIMUM
EATING
OWER
20
30
40
50
Display
60
70
80
90
100
25
%