Gas Regulation - Ariston ecoCOMBI 27 MFFI Installation And Servicing Instructions

Microcondens series, type c boilers
Hide thumbs Also See for ecoCOMBI 27 MFFI:
Table of Contents

Advertisement

3.6.4 G
AS REGULATION CHECK
Supply pressure
G20 methane
17-25 mbar
G30 butane
25-35 mbar
G31 propane
25-45 mbar
24
2
F
. 3.11
IG
1
Supply pressure check
1. Loosen screw "1" (Fig. 3.12) and insert the pressure gauge connection pipe into
the pipe tap.
2. Turn the boiler on at maximum power, enabling the "flue sweep" function (press the
Comfort key "K" for 5 seconds). The supply pressure should correspond to that
foreseen for the type of gas the boiler is designed for (See table 4C).
3. When the check is over, tighten screw "1" and make sure it is securely in place.
4. Disable the flue sweep function by pressing the reset key "H".
A
/
IR
GAS RATIO CHECK
Air/gas ratio at minimum power
To check the air/gas ratio at minimum power, proceed as follows:
1. Connect the combustion analyser to the analysis point (Fig. 3.11) after removing
the cover plate.
2. Turn the boiler on at minimum power via the test function (see paragraph 3.6.1) or
by pressing keys "K" and "H" simultaneously on the control panel. Ensure the CO
value on the analyser corresponds with the value indicated in table 4D. If this is not
the case, adjust screw "2" with a screwdriver, after removing the cap, until you
obtain the correct CO
2
minutes.
3. When the check is over, replace the cap on screw "2" (Fig. 3.11).
4. Disable operation at minimum power by pressing key "H".
Air/gas ratio at maximum power
To check the air/gas ratio at maximum power, proceed as follows:
1. With the combustion analyser already connected to the analysis point, set the
boiler to maximum power via the test function (see paragraph 3.6.1) or enabling
the "flue sweep function" by pressing the Comfort key "K" for 5 seconds.
Ensure the CO
value on the analyser corresponds with the value indicated in
2
table 4D. If this is not the case, adjust screw "4" with a screwdriver (Fig. 3.12), until
you obtain the correct CO2 reading. Allow the reading to become stable for at least
4 minutes.
2. Disable the "flue sweep function" by pressing key "H".
The "flue sweep function" is automatically disabled after 5 minutes.
3. Repeat the air/gas ratio at minimum power check (see above).
4. Disconnect the analyser, remount the cover plate and check it is securely in place.
A
/
IR
GAS RATIO SETTING
Calibration values check
CO
at minimum power
2
after 4 minutes of operation
3
reading. Allow the reading to become stable for at least 4
methane G20
butane
propane G31
4
F
. 3.12
IG
% vol
10 ±0.2
G30
% vol
11.5 ±0.2
% vol
11.5 ±0.2
2