Download Print this page

Bosch RF3224 Installation Instructions page 2

Rf receiver

Advertisement

Figure 5: Receiver with Outer Cover Removed
1 - Antenna connectors
2 - Mounting holes
3 - LED
4 - Bus and power connector
5 - Cover tamper switch
Figure 6: Connecting Antennas
1
1 - Mount one antenna here and point it upwards.
2 - Mount second antenna at one of these locations.
3 - Preferred location (provides polar diversity)
3.4
Setting Receiver Options
Note: Changing these settings requires removing the power to
the receiver and then reapplying for the changes to take affect.
Set the receiver address option as required (see Figure 7).
Figure 7: Address
1
ADDR
1 - Address
2 - Receiver #1 (default). Jumper left on pin for storage only.
3 - Receiver #2
© 2003 Bosch Security Systems
130 Perinton Parkway, Fairport, NY 14450-9199 USA
Customer Service: (800) 289-0096; Technical Support: (888) 886-6189
1
2
3
4
R
B
G
Y
ADDR
5
2
3
2
R
B
G
Y
3
4.0
Wiring and Power Up
4.1
Wiring the Receiver to the Control Panel
1. Disconnect power from the control panel.
2. Connect the D6412 Option Bus terminals to the
RF3224 receiver terminals as shown in Figure 8, using a
minimum of 22 AWG (0.8 mm diameter) wire.
The wire length between the receiver and the control
panel should not exceed 300 m (1000 ft.). Adding
supplementary devices to the bus may reduce the
maximum distance. Shielded cable is not required. Do
not use twisted pair wire.
Note: Fire systems installed under N FPA 72 or UL Listed
Fire Systems require the use of #18 AWG (1.2 mm) or larger
wire.
Figure 8: Connecting to the Option Bus
1
GRN
YEL
BLK
RED
1 - D6412
2 - RF3224
3. Replace the outer cover.
4. Apply power to the control panel. The red LED at the
center of the receiver illuminates.
4.2
LED Status
Table 2 describes the status of the receiver based on the
LED condition.
Table 2: LED Status
LED Condition
Meaning
On
The receiver functions normally.
Off
A power failure occurred or the receiver is not
wired correctly.
Turns on
The receiver acknowledged receiving a
Momentarily
message from a compatible transmitter.
Flashes
The receiver is being programmed with zone
Rapidly
and transmitter IDs from the D6412 Control
Panel. This condition occurs upon initialization
(power up) of the system or when new zone
information is programmed into the system. The
rapid flashing lasts for less than 1 minute.
5.0
Panel Programming
For programming information, refer to the D6412 Control