GE ZONELINE 2800 Data Manual page 16

Zoneline packaged terminal air conditioners 2800 series; 3800 series; 5800 series
Table of Contents

Advertisement

Remote Thermostat Control
Heat Pump Models
The Zoneline
800 and 5800 Series heat pump units may
®
be connected to a single-stage cooling/two-stage heating
thermostat designed for use with heat pump systems. GE
offers  thermostats compatible with the 800 and 5800
series units:
RAK147 —
RAK148D1 —
mechanical
solid-state digital
manual
manual
changeover
changeover
thermostat
thermostat
requiring 6
requiring 6
connection wires.
connection wires.
Please see page 57 for installation recommendations for the
remote thermostat wiring. Compatibility of other thermostats
considered for use with the GE Zoneline
of the customer.
The control voltage on the remote control conductors is 24 VAC.
The Class 2 Mode Switch, dip switch #4 on the auxiliary control
board on both the 800 series and the 5800 series, must be set
to the ON/UP mode to enable remote thermostat control. Refer
to installation instructions packaged with the chassis.
The fan speed for the 800 and 5800 series in remote
thermostat operation is selected by the connection of the
fan wire from the thermostat to either the HIGH or LOW
terminal on the unit. See the sketch of the unit terminals
for the location of the HIGH and LOW fan speed terminals.
Operating the unit in low fan speed reduces the operating
sound level of the unit.
When connected to a remote thermostat, the indoor air
temperature sensing is shifted from the unit to the remote
thermostat. For this reason, the units will operate slightly
differently when connected to a remote thermostat. The
following chart shows the unit operation when connected
to a remote thermostat.
Remote Thermostat Control Selection Chart For Zoneline Packaged Terminal Units
Zoneline Series
Thermostat Model
2800
800 and 5800
Thermostat wire size – up to 60 feet AWG20 – up to 66 feet AWG18
16
RAK148P1 —
solid-state digital
programmable
auto-changeover
thermostat
requiring 6
connection wires.
is the responsibility
®
Type
RAK16A1
Mechanical
RAK164D1
Digital
RAK164P1
Digital Programmable
RAK147
Mechanical
RAK148D1
Digital
RAK148P1
Digital Programmable
Temperature Boost option should not be used with remote
thermostat operation since this will cause the unit to switch to
resistance heat when outdoor temperatures are below 46ºF.
Feature
Heat Pump
Indoor Frost Control
Yes
Freeze Sentinel
Yes
Auto Fan Speed
No
Electronic
Temperature Limiting No
Switch to Resistance
Heat Based On Indoor
Determined by
Temperature
Remote Thermostat
Switch to Resistance
Heat Based On
Outdoor Temperature Yes
Reverse Cycle Defrost Yes
Simultaneous
Resistance Heat
with Heat Pump
No
Resistance Heat
Lockout
Yes
"Smart Fan"
Fan ON/AUTO Set On
Fan Cycle
Remote Thermostat
Central Desk Control Yes
Field Wiring Terminal
R
— 24V AC
GH — High-Speed Fan
Resistance Heat Models
Y
— Compressor
C
— Common - Ground
Heat Pump Models
Function
Cooling and Heating
Single Stage Cooling –
2 Stage Heating
Electric Heat
Yes
Yes
No
No
N/A
N/A
N/A
N/A
N/A
Common — Ground
White — Heater
Fan ON/AUTO Set On
Remote Thermostat
Yellow — Compressor
Black — Not Used On 2800
Yes
Green — High-Speed Fan
Green — Low-Speed Fan
Red — 24V AC
GL — Low-Speed Fan
CDC Terminal
B
— Reversing Valve
W — Heater
Common — Ground
White — Heater
Yellow — Compressor
Black — Reversing Valve
Green — High-Speed Fan
Green — Low-Speed Fan
Red — 24V AC
Low-Voltage Conductors
4
5
5
6
6
6