Summary Of Ul Requirements - NAPCO Gemini GEM-P1632 Installation Instructions Manual

Control panel/communicator
Table of Contents

Advertisement

!
Page 8
Smoke Detectors, 4-Wire:
1. ESL 445AT, 445C, 445CT, 445CR, 445CRT
2. Hochiki America SLG-12 with YBC-RL4-RA Base
3. System Sensor 2312/24T; 1412; 1412TH; 2412TH
Subtract total smoke-detector alarm current from available standby current.
Note: Any normally-open devices that do not require power from the control panel, such as pull stations and thermostats
may be used if acceptable to the Authority having Jurisdiction.
UL Compatible Smoke Detectors (Providing UL Recognition or Listing)
Manufacturer
Napco
Sentrol
System
Sensor
Note: * Voltage Rating: 8.5-13.3 VDC, Maximum Number of Detectors: 10

SUMMARY OF UL REQUIREMENTS

Residential
!
Recognized Limited-Energy Cable for initiating, indicating and supplementary circuits.
!
Initiating loops supervised if longer than 3 feet
!
FT2200 End-of-Line Relay for Fire (if using 4-wire smoke detectors)
!
Minimum alarm timeout of 5 minutes
!
Maximum exit time: 60 seconds
!
Maximum entry time: 45 seconds
!
Do not program "Swinger Shutdown", "Force Arming", "Selective Bypass" or "50 ms Loop Response"
!
"Abort Delay" may not exceed 45 seconds
!
Program "Disable Callback Download"
!
Automatic dialer may not dial a police station number that has not been dedicated for such service
!
System must be tested at least weekly under AC/battery and Battery-Only conditions
!
Replace the rechargeable battery at least every 5 years
!
If the battery is heavily discharged, replace it or have it tested by a qualified technician
!
For silent panic, connect only to UL-listed holdup devices
!
All zones must be programmed for "Priority"
!
Do not program any zones for "Keyswitch Arming"
!
System must be serviced at least once every year
!
Residential Fire and Combination Residential Fire & Burglary must program "Residential Fire"
!
Keypad Expansion (EZM) Zones are not to be used as fire zones
!
Keypad Auxiliary is not to be selected
!
The GEM-K Series Keypads must have the indicators printed on the face label (Fire, Police and Auxiliary) covered
by a supplied label if not in use.
X
GEM-P1632 Installation Instructions
4-Wire
Smoke Detector
FW-4
449AT
449CLT
449C
449CSLT
449CRT
449CTE
449CST
741U
449CSRT
742U
449CSRH
449CSST
1112
2112T
2100
2112
2112TSRB
2100T
2-Wire
Smoke Detector
Smoke Detector *
FW-2
712U
731U
701U
722U
702U
732U
702RE
711U
702RU
721U
721UT
1100
L
WI808F 8/03