Outdoor Unit Installation
3.
Flaring the pipe end
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing
downward so that the chips do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.
WARNING
• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a drier to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.
4.

Refrigerant piping

CAUTION
• Use the flare nut fixed to the main unit to prevent it from cracking and deteriorating from age.
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
• Align the centers of both flares and tighten the flare
nuts 3 or 4 turns by hand. Then tighten them fully with
the torque wrenches.
Flare nut tightening torque
Gas side
5/8 inch (15.9mm)
45.6-55.6ft • lbf
(61.8-75.4N • m)
6
Set exactly at the position shown below.
Liquid side
3/8 inch (9.5mm)
24.1-29.4ft • lbf
(32.7-39.9N • m)
(Cut exactly at
right angles.)
Flaring
A
Flare tool for R410A
Clutch-type
Clutch-type (Rigid-type)
Die
0-0.020 inch
A
(0-0.5mm)
Flare's inner surface
must be flaw-free.
[Apply oil]
Do not apply refrigeration
oil to the outer surface.
Flare nut
Do not apply refrigeration oil to
the flare nut to avoid tightening
with excessive torque.
Valve cap tightening torque
Gas side
5/8 inch (15.9mm)
35.5-44.0ft • lbf
(48.1-59.7N • m)
Service port cap tightening torque
7.9-10.8ft • lbf
(10.8-14.7N • m)
Remove burrs.
Conventional flare tool
Wing-nut type (Imperial-type)
0.039-0.059 inch
0.059-0.079 inch
(1.0-1.5mm)
(1.5-2.0mm)
Check
The pipe end must
be evenly flared in a
perfect circle.
Make sure that the
flare nut is fitted.
Apply refrigeration oil to
the inner surface of the
flare.
Liquid side
3/8 inch (9.5mm)
15.9-20.2ft • lbf
(21.6-27.4N • m)
English