Pump Down Operation; Forced Cooling Operation - Daikin RXS30LVJU Installation Manual

R410a split series
Hide thumbs Also See for RXS30LVJU:
Table of Contents

Advertisement

Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.

Forced cooling operation

Using the indoor unit ON/OFF switch
Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.)
• Forced cooling operation will stop automatically after around 15 minutes.
To stop the operation, press the indoor unit ON/OFF switch.
Using the indoor unit's remote controller
1) Press "MODE" button and select the cooling mode.
2) Press "ON/OFF" button to turn on the system.
3) Press both of "TEMP" button and "MODE" button at the same time.
4) Press "MODE" button twice. ( will be displayed and the unit will enter forced cooling operation.)
• Forced cooling operation will stop automatically after around 30 minutes.
To stop the operaion, press "ON/OFF" button.
Using the outdoor unit forced cooling operation switch
Forced cooling operation can be performed when the outdoor unit forced cooling operation switch is pressed within
around 3 minutes after power is supplied.
Press the switch (SW1). (The operation will start.)
• Forced cooling operation will stop automatically after around 15 minutes.
To stop the operation, press the switch (SW1).
Wiring
WARNING
• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or fire.
• Be sure to install a ground fault circuit interrupter breaker. (One that can handle higher harmonics.)
(This unit uses an inverter, which means that it must be used a ground fault circuit interrupter breaker capable handling
harmonics in order to prevent malfunctioning of the ground fault circuit interrupter breaker itself.)
• Use an all-pole disconnection type breaker with at least 1/8 inch (3mm) between the contact point gaps.
• When carrying out wiring connection, take care not to pull at the conduit.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.
• Do not turn on the safety breaker until all work is completed.
1) Strip the insulation from the wire (3/4inch (20mm)).
2) Connect the connection wires between the
indoor and outdoor units so that the terminal
numbers match. Tighten the terminal screws
securely. We recommend a flathead
screwdriver be used to tighten the screws.
English
S102
S2
LED-A
SW4
Forced
cooling
operation
SW1
switch (SW1)
Firmly fix the wires with
the terminal screws.
Use AWG16 if the connection wire
length is less than 32.8ft (10m), or
AWG14 if it is 32.8ft (10m) or more.
1
Indoor
2
3
unit
Service port
Gas stop valve
Liquid stop valve
Outdoor unit
1 2 3
L
L
GR
1
2
Use AWG 14 wires.
Safety
Ground fault
breaker
circuit interrupter
20A
Ground
Hexagonal
wrench
Close
valve cap
Power supply
60Hz 208-230V
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rks36lvjuRxs36lvjuRks30lvju

Table of Contents