BeFore STarTing
CauTion
The engine's exhaust contains harmful emissions.
alWaYS have adequate ventilation when operating.
1. Place the Control Power switch (Figure 18) on the
digital control panel in the up position (ON).
Figure 18. Control Power Switch (ON)
2. Place the voltage selector switch (Figure 19) in the
desired voltage setting position. The corresponding
Voltage Status LED on the control panel will light to
indicate the selected voltage (Figure 20).
277/480
3
Figure 19. Voltage Selector Switch
120/208 3Ø Position
LIGHTS IF
SELECTED
Figure 20. Voltage Status LEDs
3. If it is necessary to prime engine before starting (such
as after changing fuel filter or running out of fuel), place
the fuel valves in the prime position (Figure 21). Place
the fuel priming switch (Figure 22) in the up position.
page 34 — Sg1400C3 STudio generaTor • operaTion manual — rev. #0 (10/05/11)
ON (UP)
120/208
3
120/240
1
FUEL VALVES IN
PRIME MODE
Figure 21. Fuel Valves (Prime Mode)
Figure 22. Fuel Priming Switch (ON)
4. After priming is complete, release the fuel priming
switch. Place the fuel valves in the run mode (Figure
23).
FUEL VALVES IN
RUN MODE
Figure 23. Fuel Valves (Run Mode)
5. Verify that all three circuit breakers (Figure 24)are in
the on position prior to starting the engine.
VERIFY CIRCUIT
BREAKERS ARE ON
Figure 24. Circuit Breakers (ON)

StartuP

ON (UP)
ON
Electronic Trip Unit
Instantaneous Trip Setting - Amps
Test
Push to Trip
E
A — 500
E — 1250
D
F
B — 600
F — 1500
450 AMP
C
G
C — 800
G — 2000
LONG — INST.
B
H
D — 1000
H — 2500
Status
A