Table PD-20 — Auxiliary Electric Heat Capacity
Unit
Tons
Model No.
12½, 15
WC
150B3, B4, BW
*
WC
180B3, B4, BW
*
20
WC
240B3, B4, BW
*
Notes:
1. Does not include indoor fan power or heat.
2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP =(
* Indicates both downflow and horizontal units.
PKGP-PRC001-EN
Performance
Data
Table PD-19— Heating Capacity Correction Factors
% Variation of Nominal CFM
Total Gross Capacity Multiplier
2
Total
KW
MBh
Input
1
Output
1
18.00
61.00
36.00
123.00
54.00
184.00
36.00
123.00
54.00
184.00
72.00
246.00
Voltage
)2 x rated cap.
Rated Voltage
Table PD-22— Air Temperature Rise Across Electric Heaters (Degree F)
KW
9.00
17.30
18.00
27.00
36.00
54.00
72.00
Table PD-23 — Electric Heater Temperature Rise Correction Factors
% Variation From Nominal CFM
Temperature Rise Multiplier
(12½ - 20 Tons)
- 20
- 10
.96
.98
Stage 1
No. of
KW
MBh
Stages
Input
1
Output
1
18.00
61.00
2
18.00
61.00
2
36.00
123.00
2
18.00
61.00
2
36.00
123.00
2
36.00
123.00
Table PD-21 —Electric Heater Voltage
Correction Factors (Applicable to Auxiliary
Heat Capacity)
Nominal
Voltage
240
480
600
12½ Ton
5000 CFM
Three Phase
Stages
WC
150B
*
1
1
1
11.4
2
2
23.0
2
34.1
2
- 20
- 15
- 10
- 5
1.25
1.17
1.11
1.05
0
+ 10
+ 20
1.0
1.01
1.02
Stage 2
KW
MBh
1
Input
1
Output
1
18.00
61.00
18.00
61.00
18.00
61.00
18.00
61.00
36.00
123.00
Distribution
Capacity
Voltage
Multiplier
208
0.75
230
0.92
240
1.00
440
0.84
460
0.94
480
1.00
540
0.81
575
0.92
600
1.00
15 Ton
20 Ton
6000 CFM
8000 CFM
Three Phase
Three Phase
WC
180B
WC
240B
*
*
9.5
19.0
14.2
28.4
21.3
28.5
0
+5
+10
+15
+20
1.00
0.95
0.91
0.87
0.83