Trane Voyager PKGP-PRC001-EN User Manual page 16

Packaged heat pumps 12 1/2 to 20 tons — 60 hz
Table of Contents

Advertisement

Table PD-4 — Gross Cooling Capacities (MBh) 20 Ton Downflow Three Phase WCD240B
Enter.
CFM
Dry
Bulb
61
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 212.0 177.0 233.0 137.0 243.0 89.7 198.0 173.0 228.0 133.0 244.0 87.3 179.0 164.0 211.0 130.0 239.0 83.1 160.0 154.0 189.0 115.0 225.0 76.8
80 219.0 218.0 234.0 165.0 246.0 122.0 204.0 204.0 229.0 168.0 247.0 123.0 188.0 188.0 212.0 160.0 240.0 118.0 172.0 172.0 190.0 150.0 225.0 112.0
7200
85 229.0 229.0 236.0 197.0 249.0 148.0 220.0 220.0 231.0 202.0 249.0 153.0 205.0 205.0 215.0 196.0 242.0 153.0 189.0 189.0 194.0 186.0 226.0 146.0
90 238.0 238.0 238.0 227.0 252.0 174.0 234.0 234.0 233.0 233.0 252.0 183.0 222.0 222.0 222.0 222.0 242.0 186.0 206.0 206.0 206.0 206.0 227.0 181.0
75 218.0 193.0 237.0 144.0 244.0 91.2 204.0 185.0 232.0 139.0 246.0 89.1 184.0 175.0 216.0 131.0 242.0 85.0 162.0 162.0 193.0 128.0 229.0 78.8
80 224.0 224.0 239.0 173.0 247.0 123.0 213.0 213.0 233.0 176.0 249.0 126.0 196.0 196.0 217.0 170.0 243.0 124.0 180.0 180.0 195.0 160.0 230.0 117.0
8000
85 234.0 234.0 241.0 207.0 250.0 150.0 228.0 228.0 235.0 213.0 252.0 158.0 215.0 215.0 221.0 210.0 244.0 159.0 197.0 197.0 197.0 197.0 230.0 155.0
90 242.0 242.0 245.0 238.0 253.0 178.0 240.0 240.0 240.0 240.0 254.0 190.0 231.0 231.0 231.0 231.0 246.0 195.0 216.0 216.0 216.0 216.0 232.0 193.0
75 223.0 201.0 238.0 148.0 245.0 93.4 209.0 196.0 235.0 145.0 248.0 90.6 189.0 186.0 220.0 138.0 244.0 86.8 168.0 168.0 196.0 136.0 232.0 80.6
80 229.0 229.0 241.0 177.0 248.0 139.0 220.0 220.0 236.0 184.0 250.0 128.0 204.0 204.0 221.0 180.0 246.0 129.0 186.0 186.0 199.0 170.0 233.0 122.0
8800
85 238.0 238.0 244.0 212.0 252.0 152.0 234.0 234.0 239.0 223.0 253.0 161.0 222.0 222.0 226.0 223.0 247.0 165.0 205.0 205.0 205.0 205.0 233.0 164.0
90 245.0 245.0 247.0 245.0 255.0 181.0 245.0 245.0 245.0 245.0 256.0 195.0 238.0 238.0 238.0 238.0 249.0 203.0 224.0 224.0 224.0 224.0 236.0 205.0
75 226.0 208.0 241.0 151.0 246.0 94.2 214.0 206.0 236.0 148.0 249.0 91.4 191.0 191.0 223.0 144.0 245.0 88.6 174.0 174.0 199.0 143.0 235.0 82.4
80 232.0 232.0 243.0 185.0 250.0 126.0 226.0 226.0 238.0 190.0 251.0 115.0 211.0 211.0 225.0 189.0 247.0 123.0 193.0 193.0 203.0 179.0 235.0 127.0
9600
85 241.0 241.0 245.0 222.0 253.0 155.0 239.0 239.0 242.0 231.0 255.0 165.0 229.0 229.0 229.0 229.0 249.0 170.0 212.0 212.0 212.0 212.0 236.0 171.0
90 248.0 248.0 247.0 247.0 256.0 184.0 248.0 248.0 248.0 248.0 258.0 200.0 243.0 243.0 243.0 243.0 252.0 210.0 231.0 231.0 231.0 231.0 239.0 215.0
Notes:
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
3. MBH = Total Gross Capacity
4. SHC = Sensible Heat Capacity
Table PD-5 — Gross Cooling Capacities (MBh) 20 Ton Horizontal Three Phase WCD240B
Enter.
CFM
Dry
Bulb
61
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
217 .0 181.0 238.0 140.0 248.0 91.4 202.0 177 .0 233.0 136.0 249.0 88.9 183.0 167 .0 215.0 132.0 244.0 84.7 163.0 157 .0 192.0 117 .0 229.0 78.3
80
224.0 223.0 239.0 168.0 250.0 124.0 208.0 208.0 233.0 171.0 251.0 126.0 192.0 192.0 216.0 163.0 245.0 121.0 175.0 175.0 194.0 153.0 229.0 114.0
7200
85
233.0 233.0 241.0 201.0 253.0 151.0 224.0 224.0 235.0 206.0 254.0 156.0 209.0 209.0 219.0 200.0 246.0 156.0 192.0 192.0 198.0 190.0 230.0 149.0
90 242.0 242.0 242.0 230.0 256.0 177.0 238.0 238.0 238.0 238.0 257.0 186.0 226.0 226.0 226.0 226.0 247.0 189.0 210.0 210.0 210.0 210.0 231.0 185.0
75
223.0 197 .0 241.0 147 .0 249.0 93.5 208.0 188.0 236.0 142.0 251.0 90.8 188.0 178.0 220.0 134.0 247 .0 86.6 165.0 165.0 196.0 130.0 233.0 80.3
80
228.0 228.0 244.0 176.0 252.0 126.0 217 .0 217 .0 237 .0 180.0 254.0 128.0 200.0 200.0 221.0 174.0 248.0 126.0 183.0 183.0 199.0 163.0 234.0 119.0
8000
85
238.0 238.0 246.0 211.0 255.0 153.0 233.0 233.0 240.0 217 .0 256.0 161.0 219.0 219.0 225.0 214.0 249.0 163.0 201.0 201.0 201.0 201.0 234.0 158.0
90 246.0 246.0 250.0 243.0 258.0 181.0 245.0 245.0 245.0 245.0 259.0 194.0 235.0 235.0 235.0 235.0 251.0 199.0 220.0 220.0 220.0 220.0 236.0 197 .0
75
228.0 205.0 243.0 151.0 250.0 95.2 213.0 200.0 239.0 147 .0 252.0 92.3 193.0 189.0 224.0 140.0 249.0 88.5 172.0 172.0 200.0 138.0 237 .0 82.1
80
233.0 233.0 245.0 181.0 253.0 142.0 224.0 224.0 240.0 187 .0 255.0 131.0 208.0 208.0 225.0 183.0 250.0 131.0 190.0 190.0 203.0 173.0 237 .0 124.0
8800
85
242.0 242.0 248.0 216.0 256.0 155.0 239.0 239.0 243.0 227 .0 258.0 165.0 227 .0 227 .0 230.0 227 .0 252.0 169.0 209.0 209.0 209.0 209.0 238.0 167 .0
90 249.0 249.0 252.0 250.0 260.0 184.0 249.0 249.0 249.0 249.0 261.0 199.0 242.0 242.0 242.0 242.0 254.0 207.0 228.0 228.0 228.0 228.0 240.0 208.0
75
231.0 212.0 245.0 153.0 251.0 96.0 218.0 210.0 241.0 151.0 253.0 93.1 195.0 195.0 227 .0 146.0 250.0 90.3 177 .0 177 .0 203.0 146.0 239.0 84.0
80
237 .0 237 .0 247 .0 188.0 254.0 128.0 230.0 230.0 243.0 194.0 256.0 117 .0 215.0 215.0 229.0 193.0 251.0 125.0 196.0 196.0 207 .0 183.0 240.0 130.0
9600
85
245.0 245.0 249.0 226.0 258.0 158.0 243.0 243.0 246.0 236.0 260.0 168.0 233.0 233.0 233.0 233.0 253.0 173.0 216.0 216.0 216.0 216.0 241.0 175.0
90 253.0 253.0 252.0 252.0 261.0 187.0 253.0 253.0 253.0 253.0 263.0 204.0 247.0 247.0 247.0 247.0 256.0 214.0 235.0 235.0 235.0 235.0 244.0 219.0
Notes:
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
3. MBH = Total Gross Capacity
4. SHC = Sensible Heat Capacity
16
Performance
Data
85
95
67
73
61
67
85
95
67
73
61
67
Ambient Temperature (F)
105
Entering Wet Bulb (F)
73
61
67
Ambient Temperature (F)
105
Entering Wet Bulb (F)
73
61
67
(20 Ton)
1 15
73
61
67
1 15
73
61
67
PKGP-PRC001-EN
73
73

Hide quick links:

Advertisement

Table of Contents
loading