Table PD-14 — 12½ Ton Downflow Three Phase Heating Capacities (Net) WCD150B3, B4, BW at 5000 CFM
Integrated Heating Capacity (MBh/1000)
Outdoor
At Indicated Indoor Dry Bulb Temp.
Temp.
F.
60
70
-8
51.9
50.3
-3
56.8
55.3
2
62.1
60.7
7
67.9
66.4
12
74.1
72.6
17
80.7
79.1
22
87.8
86
27
95.3
93.3
32
103.2
101
37
111.1
108.6
42
119.2
116.4
47
138.6
135.3
52
148.1
144.5
57
155.6
151.4
62
168.8
164.2
67
179.3
174.3
72
189.9
184.5
For other airflow conditions, see heating capacity correction factor (Table PD-19).
Net Heating Capacity and Power Input include indoor fan heat at nominal cfm and .35 inch ESP. To obtain net heating at other conditions,
subtract fan heat at this condition and add fan heat at new condition.
Heating capacities and powers are integrated to include the effects of defrost in the frost region.
All heating capacities and power (kW) are at 70% OD relative humidity.
Table PD-15— 12½ Ton Horizontal Three Phase Heating Capacities (Net) WCH150B3, B4, BW at 5000 CFM
Integrated Heating Capacity (MBh/1000)
Outdoor
At Indicated Indoor Dry Bulb Temp.
Temp.
F.
60
70
-8
48.2
46.6
-3
52.7
51.3
2
57.7
56.3
7
63.1
61.7
12
68.9
67.5
17
75.2
73.6
22
81.8
80.1
27
88.9
87
32
96.3
94.2
37
103.7
101.4
42
111.3
108.7
47
137.3
133.9
52
146.8
143.1
57
154.4
150.1
62
167.7
162.9
67
178.1
173.1
72
188.8
183.4
For other airflow conditions, see heating capacity correction factor (Table PD-19).
Net Heating Capacity and Power Input include indoor fan heat at nominal cfm and .40 inch ESP. To obtain net heating at
other conditions, subtract fan heat at this condition and add fan heat at new condition.
Heating capacities and powers are integrated to include the effects of defrost in the frost region.
All heating capacities and power (kW) are at 70% OD relative humidity.
(12½ Ton)
Total Power in Kilowatts At
Indicated Indoor Dry Bulb Temp.
75
80
60
49.6
49
9.56
54.6
54
9.61
60
59.4
9.74
65.7
65.1
9.85
71.9
71.1
9.98
78.3
77.6
10.13
85.1
84.3
10.3
92.3
91.4
10.48
99.9
98.9
10.68
107.4
106.3
10.89
115.1
113.9
11.11
133.8
132.3
11.93
142.9
141.2
12.2
149.4
147.4
12.46
161.9
159.7
12.8
171.8
169.4
13.17
181.8
179.1
13.55
Total Power in Kilowatts At
Indicated Indoor Dry Bulb Temp.
75
80
60
46
45.4
9.18
50.6
50
9.23
55.7
55.1
9.35
61.1
60.4
9.46
66.8
66.1
9.58
72.9
72.1
9.73
79.3
78.4
9.88
86
85.1
10.06
93.1
92.1
10.25
100.2
99.1
10.45
107.5
106.3
10.67
132.4
130.9
11.53
141.4
139.8
11.8
148.1
146.1
12.04
160.7
158.4
12.37
170.6
168.2
12.72
180.7
178
13.1
70
75
80
10.37
10.83
11.32
10.45
10.92
11.42
10.55
11.03
11.53
10.72
11.2
11.71
10.87
11.36
11.88
11.03
11.53
12.06
11.22
11.72
12.26
11.41
11.92
12.48
11.62
12.14
12.7
11.84
12.37
12.94
12.07
12.61
13.18
12.96
13.53
14.14
13.25
13.83
14.43
13.49
14.06
14.67
13.86
14.43
15.04
14.24
14.82
15.44
14.64
15.23
15.85
70
75
80
9.96
10.4
10.87
10.03
10.48
10.96
10.13
10.58
11.07
10.29
10.75
11.24
10.43
10.9
11.4
10.59
11.07
11.58
10.77
11.25
11.77
10.96
11.45
11.98
11.16
11.66
12.2
11.37
11.88
12.42
11.6
12.11
12.66
12.52
13.07
13.66
12.8
13.36
13.96
13.04
13.6
14.19
13.39
13.95
14.55
13.76
14.33
14.93
14.15
14.73
15.33
PKGP-PRC001-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents