CNT-SVP01C-EN
9. In the Decimal Places list, click the number of digits you want to
appear to the right of the decimal when the variable value is dis-
played.
10. If the variable has Tracer Summit as its source, under Communica-
tions Loss Value, type the value you want to appear if Tracer Summit
communications are lost to the Tracer MP580/581.
11. If the variable has the operator display and service tool as its source,
under Value, type the value you want the variable to have.
Note:
The variable value is saved once every 24 hours. If a power loss
occurs, the variable value is set to the last saved value.
12. Complete one of the following options:
Click another variable name in the Name list to edit another vari-
able.
Click another tab to set up another item.
Click the Download button to send your changes to the Tracer
MP580/581. (If the Security Logon dialog box appears, log on.)
Click Close to close the Configuration dialog box.

Configuring user security

A user who has security supervisor access can set up security privileges
for up to eight users, giving each different access privileges, for both the
Tracer MP580/581 operator display and the Rover service tool. Any user
can view all displays on the Tracer MP580/581 operator display; however,
a security supervisor can set up security to prevent unauthorized users
from changing variables or overriding outputs at the operator display.
A security supervisor can also set up security to prevent unauthorized
users from downloading or deleting variables, overriding inputs, down-
loading or deleting a Tracer graphical program, clearing memory on the
controller, and performing a flash download to the controller.
After security is established, users are prompted to log on with a pass-
word when they attempt to perform security-protected functions.
Note:
A logged-on user loses access to security-protected functions if
an action is not performed for 30 minutes.